Honeywell R0512 manual Attributes

Models: R0512

1 86
Download 86 pages 48.24 Kb
Page 19
Image 19

EXCEL 50/100/500/600/800

ATTRIBUTES

In the datapoint description, the alarms can be influenced using the functions described below (see also Table 6 on page 17).

Alarm type For each datapoint in the datapoint description, the user can determine whether the signals generated are to be treated as critical or non-critical alarm.

Alarm delay An alarm signal can be delayed by entering an alarm delay time. An alarm signal will be generated only if an alarm continues uninterrupted during the alarm delay time.

Suppress alarm If an alarm signal is not desired from a particular datapoint, this can be fixed in the datapoint description. Thus, all the alarm signals relevant to the particular datapoint and the "Operating Mode" alarm types are suppressed.

Fig. 7. Alarm condition depending on point value and Suppress Alarm status

Fig. 7 shows an example of a changing point value that rises above and falls below the limit Max 2. If Suppress Alarm is not active, then the alarm condition switches between normal to alarm, according to the limit Max 2. If Suppress Alarm is active, then the alarm condition remains normal unless Suppress Alarm is switched off before the point value falls below the limit Max 2. Regardless of the setting of the Alarm suppression flag, an alarm is entered into the controller's history buffer and is also available in the EBI alarm report.

Point alarm It is possible to view all datapoints at the operator interfaces for which the limit value (analog point) or the alarm status (digital point) is currently exceeded.

Driven by a menu, the user address and the accompanying alarm text are displayed on the XI581 (not with XCL5010, Excel 100C) or XI582 operator interfaces or Excel 50 MMI.

On the XL-Online operator interface, a datapoint within the framework of the datapoint description can be seen in all four password levels. If a current alarm is present for the point in question, the attribute “Point in Alarm” produces the display “Yes”, otherwise “No”.

Within the framework of the datapoint description, it is possible, under the attribute “Alarm text”, to enter an alarm text of up to 18 characters in addition to the prepro- grammed text. There are 256 alarm texts in total.

Table 6 presents a summary of various alarm types and attributes.

Table 6. Alarm summary

alarm type/attributes

alarm status

enter alarm

alarm

point in

no. of prepro-

supplementary

delay time

suppression

alarm

grammed texts

text

 

 

Limit Values

selection in DPD*

possible

possible

X

8

possible

Alarm Status

selection in DPD*

possible

possible

X

2

possible

 

 

 

 

 

 

 

Maintenance Alarm

selection in DPD*

-

possible

-

1

-

Totalizer

selection in DPD*

-

possible

-

1

-

Operating Mode

always critical

-

possible

-

2

-

 

 

 

 

 

 

 

System Alarms

always critical

-

-

-

approx. 110

-

17

EN2B-0092GE51 R0512

Page 19
Image 19
Honeywell R0512 manual Attributes