EXCEL 50/100/500/600/800

TIME PROGRAMS

Time programs allow you to set values and control states for specific datapoints at specific times. You can adapt time programs to suit the structure of your system.

Network-wide time synchronization Time synchronization of all devices connected to the system bus is carried out by the controller designated as the synchronization master. Synchronization is based on date, hours, minutes, and seconds to an accuracy of ± 120 seconds (see also "Network-Wide Controller Time Synchronization" on page 55).

Structure

Flexible time programs An Excel 50/100/500/600/800 time program can consist of several individual time programs. You define these individual time programs according to their function and assign a name to each one. This means you can generate a time program for each section of your system or building.

Time programs are created on the basis of the following modules:

daily programs

weekly programs

annual programs

Further, these modules can be modified as needed using the following two functions:

the special day list

the “TODAY” function

Daily programs are combined to form a weekly program. The weekly program is then automatically copied repeatedly to form the annual program. If you need to execute a different daily program on certain days of the year, you can enter the customized daily program directly in the annual program.

The special day list and the "TODAY" function are available as additional features. The special day list allows you to mark specific days as being legal holidays. You can also use the special day list for floating legal holidays, for example Good Friday and Easter Monday. The "TODAY" function allows you to overwrite time program assignments "ad hoc" for a defined time period without permanently changing the entire time program.

Individual Time Programs

Daily Program

Daily programs are the basic building blocks of any time program. Using daily programs, you enter the switching times with the desired setpoints and switching conditions for the datapoints. When preparing a daily program and assigning the name, there is initially no specific relationship to a particular day in the week. The modular structure of the time program makes it possible for the user to establish various different daily programs, keep them in a library, and to include them in the weekly program as desired. The user is free to extend the list of daily programs to meet his special requirements.

The repeated use of the same daily program is also possible (for example, the same daily program can apply from Monday to Friday in the weekly program). Changes in a daily program are immediately effective in the weekly and annual programs as well as in the special day list.

A daily program can also have the name "Sundays and holidays", for example. The names of the daily program provide a reference to the switching points. In the "Workday 22 hr" daily program, the setpoint is reduced from 22.0°C to 12.0°C at 22.00 hr.