Hoshizaki SRH/3 KM-1900SAH/3 Close the low-side valve and high-side valve on the gauge manifold

Models: SRH/3 KM-1900SAH/3 SRH3 KM-2500SWH3 SRH3 KMH-2000SWH/3 SWH/3 KM-1301SAH/3 SWH3-M KM-1601SAH/3 SRH/3 KM-1400SWH-M SRH/3 KM-2100SWH3 SRH/3

1 101
Download 101 pages 53.65 Kb
Page 53
Image 53

4)Close the low-side valve and high-side valve on the gauge manifold.

5)Disconnect the gauge manifold hose from the vacuum pump and attach it to a refrigerant service cylinder. Remember to loosen the connection and purge the air from the hose. For the required refrigerant charge, see the rating label inside the icemaker. Hoshizaki recommends only virgin refrigerant or reclaimed refrigerant which meets ARI Standard 700 (latest edition) be used.

6)A liquid charge is required when charging an R-404A system (to prevent fractionation). Place the service cylinder on the scales; if the service cylinder is not equipped with a dip tube, invert the service cylinder, then place it on the scales. Open the high-side valve on the gauge manifold.

7)Allow the system to charge with liquid until the proper charge weight is met.

8)If necessary, add any remaining charge to the system through the low-side.

NOTICE! To prevent compressor damage, use a throttling valve or liquid dispensing device to add the remaining liquid charge through the low-side refrigerant service valve with the icemaker running.

9)Close the high and low-side service valves, then close the high and low-side gauge manifold valves. Disconnect the gauge manifold hoses.

10)Cap the refrigerant service valves to prevent a possible leak.