Alarm text

Description

 

 

Manual Load Dumped

The load power is off. This alarm is used to record the date and time of an

 

EPO event.

 

 

On Battery

The UPS is using the battery to power the load.

 

 

On Boost

The UPS detected a low input condition and is increasing input voltage to a

 

nominal level.

 

 

On Buck

The UPS detected a high input condition and is reducing input voltage to a

 

nominal level.

 

 

Output Out of Range

Measured output voltage has exceeded the upper voltage limit

 

specification for normal operation.

 

Measured output voltage is less than the lower voltage limit specification

 

for normal operation.

 

Measured output frequency is outside the upper or lower frequency limit

 

specification for normal operation.

 

 

Overload

Overload alarms are sent based on the individual UPS model overload

 

protection specifications that are available in the UPS documentation.

 

The load on the UPS output phase exceeds its rated current or power by

 

more than a small margin over 100%. The inverter can only sustain this

 

overload for a short time without shutting down because of overheating.

 

 

Remote Agent Not

A Remote Agent is not communicating with the management module to

Connected

which it is associated.

 

 

Shutdown Imminent

The UPS has entered a state where it might abruptly shut down without

 

further notice. It might continue to operate indefinitely, even with this alarm

 

being issued.

 

 

Shutdown Pending

A condition in the UPS will lead to the loss of power to the loads in less than

 

the Low Battery Time, unless the condition is cleared or removed.

 

 

Site Wiring Fault

There is a fault in the input wiring, other than Phase Rotation (for example,

 

Ground/Neutral reversed).

 

 

Temperature Out of

An ambient temperature probe has detected that the temperature is

Range

above its upper limit.

 

A heatsink at an unspecified location in the UPS has failed.

 

An input or output transformer used by the UPS has exceeded its upper

 

temperature limit.

 

 

UPS Not Connected

The management module is unable to communicate with the UPS.

 

 

UPS Started On Battery

The UPS has been started on battery when AC input power is not present.

 

This alarm is used to record the date and time of this event.

 

 