Alarm text | Description |
|
|
Manual Load Dumped | The load power is off. This alarm is used to record the date and time of an |
| EPO event. |
|
|
On Battery | The UPS is using the battery to power the load. |
|
|
On Boost | The UPS detected a low input condition and is increasing input voltage to a |
| nominal level. |
|
|
On Buck | The UPS detected a high input condition and is reducing input voltage to a |
| nominal level. |
|
|
Output Out of Range | • Measured output voltage has exceeded the upper voltage limit |
| specification for normal operation. |
| • Measured output voltage is less than the lower voltage limit specification |
| for normal operation. |
| • Measured output frequency is outside the upper or lower frequency limit |
| specification for normal operation. |
|
|
Overload | • Overload alarms are sent based on the individual UPS model overload |
| protection specifications that are available in the UPS documentation. |
| • The load on the UPS output phase exceeds its rated current or power by |
| more than a small margin over 100%. The inverter can only sustain this |
| overload for a short time without shutting down because of overheating. |
|
|
Remote Agent Not | A Remote Agent is not communicating with the management module to |
Connected | which it is associated. |
|
|
Shutdown Imminent | The UPS has entered a state where it might abruptly shut down without |
| further notice. It might continue to operate indefinitely, even with this alarm |
| being issued. |
|
|
Shutdown Pending | A condition in the UPS will lead to the loss of power to the loads in less than |
| the Low Battery Time, unless the condition is cleared or removed. |
|
|
Site Wiring Fault | There is a fault in the input wiring, other than Phase Rotation (for example, |
| Ground/Neutral reversed). |
|
|
Temperature Out of | • An ambient temperature probe has detected that the temperature is |
Range | above its upper limit. |
| • A heatsink at an unspecified location in the UPS has failed. |
| • An input or output transformer used by the UPS has exceeded its upper |
| temperature limit. |
|
|
UPS Not Connected | The management module is unable to communicate with the UPS. |
|
|
UPS Started On Battery | The UPS has been started on battery when AC input power is not present. |
| This alarm is used to record the date and time of this event. |
|
|
Alert messages 106