HP A1356A, A6584A, A1354A, A1353A, J4373A, J4370A, J4367A manual Shutdown Events menu

Models: A6584A

1 120
Download 120 pages 46.74 Kb
Page 73
Image 73

 

Low Battery—Selected

Low Battery—Deselected

 

 

 

Shutdown Settings

The management module initiates

The management module initiates

Conserve Battery Power

system shutdowns after the specified

system shutdowns after the specified

delay when the UPS begins to

delay when the UPS begins to

 

 

operate on battery power, unless

operate on battery power. If a low

 

the UPS issues a low battery alarm

battery alarm occurs during the

 

before the shutdowns are initiated.

delay countdown, the management

 

If a low battery alarm occurs during

module ignores the low battery

 

the delay countdown, the

alarm and continues to observe the

 

management module ignores the

On Battery shutdown delay setting.¹

 

On Battery settings and observes

 

 

the Low Battery shutdown delay

 

 

setting.

 

 

 

 

Shutdown Settings

The management module initiates

The management module initiates

Maximize Runtime

system shutdowns when the UPS

system shutdowns when the UPS

runtime reaches zero, unless the

runtime reaches zero. If a low

 

 

UPS issues a low battery alarm

battery alarm occurs during the

 

before the shutdowns are initiated.

runtime countdown, the management

 

If a low battery alarm occurs during

module ignores the low battery

 

the runtime countdown, the

alarm and continues to observe the

 

management module ignores the

runtime countdown.¹

 

runtime remaining and observes the

 

 

Low Battery shutdown delay setting.

 

 

 

 

Shutdown Settings

The management module initiates

The management module does not

Do Not Shutdown

system shutdowns when the UPS

initiate any type of system shutdown.

issues a low battery alarm. The

Power is maintained until the battery

 

 

management module observes the

is depleted.²

 

Low Battery shutdown delay setting.

 

 

 

 

¹Selecting this option might result in an ungraceful shutdown. The amount of remaining runtime cannot be accurately predicted after a low battery warning is issued.

² Running batteries to depletion can cause an ungraceful shutdown if a second power failure occurs before the batteries have fully charged.

4.Enter the amount of time to wait before restarting the attached device in the Restart Settings column. This option allows utility power to stabilize and disks in shared storage configurations to spin up before the server restarts.

5.Do one of the following:

o Click Save Settings to save the information.

o Click Refresh Page to cancel changes and restore the page settings to the last saved configuration.

o Click Help to view online help.

Shutdown Events menu

Click Shutdown Events in the left navigation frame to display the Shutdown Events screen. In addition to the typical events (such as power fail events) causing shutdowns, this screen enables administrators to configure other events to trigger a shutdown.

When a shutdown event occurs, the management module gracefully shuts down all attached devices and UPS load segments.

To specify an event for shutdown:

HP UPS Management Module web interface 73

Page 73
Image 73
HP A1356A, A6584A, A1354A, A1353A, J4373A, J4370A, J4367A manual Shutdown Events menu