HP J4373A Battery Test did not run, Browser incorrectly displays English or Japanese characters

Models: A6584A

1 120
Download 120 pages 46.74 Kb
Page 88
Image 88

Battery Test did not run

Possible Cause: The UPS is On Battery.

Action: The UPS must be in a certain state before the battery test runs. For more information, refer to the section, "Parameters menu option ("Parameters menu" on page 51)."

Browser does not display the web interface for an installed management module

Action:

1.Be sure that the IP address and port number are correct. The default port number for non-secure browser connection is port 80. The default port number for secure SSL browser connection is 443.

2.Be sure that the web interface (HTTP/HTTPS) is enabled on the management module.

Browser incorrectly displays English or Japanese characters

Possible Cause: Another user with different language settings logs in to the web interface.

Action: Log out of the web interface, close the browser window, and then sign in to the web interface again.

Troubleshooting 88