J. T. Eaton LCX9000 user manual

Models: LCX9000

1 128
Download 128 pages 41.65 Kb
Page 20
Image 20
Manual background

LCX9000 Liquid-Cooled Drives User Manual

January 2007

Table 1-3: Power Ratings and Dimensions of Liquid-Cooled Drive, Supply Voltage 525 – 690V AC

 

Drive Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current

 

 

Electrical Output Power

 

 

 

 

 

 

 

 

 

 

 

Thermal

Rated

Rated

Optimum

Optimum

Power Loss

 

Catalog

Ith

Cont. IL

Cont. IH

Motor at Ith

Motor at Ith

c/a/T

Chassis

Number

(A)

(A)

(A)

525V (kW)

690V (kW)

(kW)

 

 

 

 

 

 

 

 

LCX170A0-5

170

155

113

110

160

7.5/0.4/7.9

CH61

 

 

 

 

 

 

 

 

LCX208A0-5

208

189

139

132

200

9.0/0.5/9.5

CH61

 

 

 

 

 

 

 

 

LCX261A0-5

261

237

174

160

250

6.5/0.3/6.8

CH61

 

 

 

 

 

 

 

 

LCX325A0-5

325

295

217

200

300

7.5/0.4/7.9

CH72

 

 

 

 

 

 

 

 

LCX385A0-5

385

350

257

250

355

9.0/0.5/9.5

CH72

 

 

 

 

 

 

 

 

LCX416A0-5

416

378

277

250

355

9.4/0.5/9.9

CH72

 

 

 

 

 

 

 

 

LCX460A0-5

460

418

307

300

400

10.0/0.5/10.5

CH72

 

 

 

 

 

 

 

 

LCX502A0-5

502

456

335

355

450

12.0/0.6/12.6

CH72

 

 

 

 

 

 

 

 

LCX590A0-5

590

536

393

400

560

13.0/0.7/13.7

CH63

 

 

 

 

 

 

 

 

LCX650A0-5

650

591

433

450

600

16.0/0.8/16.8

CH63

 

 

 

 

 

 

 

 

LCX750A0-5

750

682

500

500

700

18.0/0.9/18.9

CH63

 

 

 

 

 

 

 

 

LCX820A0-5

820

745

547

560

800

19.0/1.0/20.0

CH74

 

 

 

 

 

 

 

 

LCX920A0-5

920

836

613

650

850

21.3/1.2/22.5

CH74

 

 

 

 

 

 

 

 

LCXH10A0-5

1030

936

687

700

1000

22.0/1.1/23.1

CH74

 

 

 

 

 

 

 

 

LCXH11A0-5

1180

1073

787

800

1100

25.0/1.3/26.3

CH74

 

 

 

 

 

 

 

 

LCXH13A0-5

1300

1182

867

900

1200

31.0/1.6/32.6

CH74

 

 

 

 

 

 

 

 

LCXH15A0-5

1500

1364

1000

1000

1400

38.0/1.9/39.9

CH74

 

 

 

 

 

 

 

 

LCXH18A0-5

1850

1682

1233

1250

1650

39.6/2.0/41.6

2xCH74

 

 

 

 

 

 

 

 

LCXH21A0-5

2120

1927

1413

1450

1900

45.0/2.4/47.4

2xCH74

 

 

 

 

 

 

 

 

LCXH23A0-5

2340

2127

1560

1600

2100

55.8/2.9/58.7

2xCH74

 

 

 

 

 

 

 

 

LCXH27A0-5

2700

2455

1800

1850

2450

68.4/3.4/71.8

2xCH74

 

 

 

 

 

 

 

 

LCXH31A0-5

3100

2818

2066

2150

2800

2xCH74

 

 

 

 

 

 

 

 

Ith = Thermal maximum continuous RMS current. Dimensioning can be done according to this current if the process does not require any overloadability or the process does not include any torque ripple.

IL = Low overloadability current. Allows +10% torque ripple. 10% exceeding can be continuous.

IH = High overloadability current. Allows +50% torque ripple. 50% exceeding can be continuous.

All values with cosϕ = 0.83 and efficiency = 97%.

c/a/T: c = power loss into coolant; a = power loss into air; T = total power loss; power losses of input chokes not included. All power losses obtained using max. supply voltage and switching frequency of 3.6 kHz.

If some other mains voltage is used, apply the formula P = 3 Un In cosϕ to calculate the Liquid-Cooled drive output power.

The enclosure class for all Liquid-Cooled drives is IP00.

1-8

For more information visit: www.EatonElectrical.com

MN04005001E

Page 20