Load Test with Motor

LCX9000 Liquid-Cooled Drives User Manual

 

 

 

January 2007

Table A-1: Fault Codes (Continued)

 

 

 

 

 

Fault

 

 

 

Code

Fault

Possible Cause

Solution

 

 

 

 

 

 

 

 

45

Device added

• option board or device added

Reset.

 

(different type)

• option board of different type or

Note: No Fault Time Data Record is

 

 

drive of different power rating

made.

 

 

added

Note: Application parameter values

 

 

 

restored to default.

 

 

 

 

50

Analog input

Current at the analog input is

Check the current loop, signal source

 

sel. signal range

<4 mA.

and wiring.

 

4 to 20 mA)

• control cable is broken or loose

 

 

 

• signal source has failed.

 

51

External fault

Digital input failed.

Check source of trigger.

 

 

 

 

52

Keypad

There is no connection between the

Check the keypad connection and

 

communication

control keypad and the drive.

keypad cable.

 

fault

 

 

 

 

 

 

53

Fieldbus fault

The data connection between the

Check installation.

 

 

fieldbus master and the fieldbus

If installation is correct contact your

 

 

board is broken.

Cutler-Hammer distributor.

 

 

 

 

54

Slot fault

Defective option board or slot.

Check that the board is properly

 

 

 

installed and seated in slot. If the

 

 

 

installation is correct, contact your

 

 

 

Cutler-Hammer distributor.

 

 

 

 

56

PT100 board

Temperature limit values set for the

Determine the cause of the high

 

temperature fault

PT100 board parameters have been

temperature.

 

 

exceeded.

 

 

 

 

 

Programmable.

 

 

“A” faults only.

 

 

Load Test with Motor

1.Connect the motor cables and check the right phase order. Also check that the motor rotates freely.

2.Check liquid cooling system operation

3.Turn on the supply voltage and ensure that all input phases are connected to the unit.

4.Check DC link voltage by measuring with multimeter and compare the value to the one on monitoring page V1.8.

5.Select the application of your choice and set the needed parameters.

6.Start the operation with lower Current Limit value and long Acceleration/Deceleration times.

7.If Closed Loop control mode is used, check direction of encoder and make necessary Closed Loop parameter settings. Check the correct operation of the encoder by running the system in open loop and check the signals in the expander board menu.

8.Run the motor without load between minimum and maximum frequencies and check the unit output current with a current clamp. Compare the value to the one on monitoring page V1.4.

9.Load the motor to nominal value if possible and repeat the current measurement. Follow the Unit Temperature value on page V1.9.

A-4