Input Chokes

LCX9000 Liquid-Cooled Drives User Manual

January 2007

Input Chokes

The input choke carries out several functions in the Cutler-Hammer liquid-cooled drive. Connection of the input choke is necessary except if you have a component in your system that performs the same tasks (e.g. a transformer). The input choke is needed as an essential component for motor control, to protect the input and DC-link components against abrupt changes of current and voltage as well as to function as a protection against harmonics.

The input chokes are included in the standard delivery of Cutler-Hammer liquid-cooled drives. However, you can also order your drive without the choke.

The Cutler-Hammer chokes listed in Table 2-16are meant for supply voltages of 400 – 500V and 525 – 690V.

Table 2-16: Input Choke Dimensioning, 6-Pulse Supply

Converter

Converter

 

 

Nominal

 

Amperages

Amperages

 

Thermal

Inductance

Calculated

(400 – 500V AC)

(690V AC)

Choke Type

Current (A)

(µH) A/B

Loss (W)

 

 

 

 

 

 

 

 

16

– 22

12

– 23

CHK0023N6A0

23

1900

145

 

 

 

 

 

 

 

 

31

– 38

31

– 38

CHK0038N6A0

38

1100

170

 

 

 

 

 

 

 

 

45

– 61

46

– 62

CHK0062N6A0

62

700

210

 

 

 

 

 

 

 

 

72

– 87

72

– 87

CHK0087N6A0

87

480

250

 

 

 

 

 

 

 

 

105

– 140

105

– 140

CHK0145N6A0

145

290

380

 

 

 

 

 

 

 

 

168

– 261

170

– 261

CHK0261N6A0

261

139/187

460

 

 

 

 

 

 

 

 

300

– 385

325

– 385

CHK0400N6A0

400

90/126

610

 

 

820

– 1180

 

 

 

 

 

 

1850 – 2340

 

 

 

 

460

– 520

416

– 502

CHK0520N6A0

520

65/95

810

1370

(CH74)

1300 – 1500

 

 

 

 

 

 

2700 – 3100

 

 

 

 

590

– 650

590

– 650

CHK0650N6A0

650

51/71

890

1640

 

1700 – 1900

 

 

 

 

 

 

 

 

 

 

 

730

 

750

CHK0750N6A0

750

45/61

970

2060

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

820

 

 

CHK0820N6A0

820

39/53

1020

2300

 

 

 

 

 

 

 

920

– 1030

 

CHK1030N6A0

1030

30/41

1170

 

 

 

 

 

 

 

 

1150

 

 

CHK1150N6A0

1150

26/36

1420

 

 

 

 

 

 

 

 

2470

– 2950

 

CHK0520N6A0

520

65/95

810

 

 

 

 

 

 

 

 

3710

 

 

CHK0650N6A0

650

51/71

890

 

 

 

 

 

 

 

 

4140

 

 

CHK0750N6A0

750

45/61

970

 

 

 

 

 

 

 

 

Inductances for different supply voltages: A = 400 – 480V AC, B = 500 – 690V AC. See Table 2-17.

Converter amperages written in bold italic require three (3) chokes of the designated kind per unit with 6-pulse supply.