Cooling

LCX9000 Liquid-Cooled Drives User Manual

January 2007

Cooling

Instead of using air for cooling, Cutler-Hammer Liquid-Cooled drives are cooled with liquid. The liquid circulation of the drive is usually connected to a heat-exchanger (liquid-liquid/ liquid-air) which cools down the liquid circulating in the cooling elements of the drive. The cooling agents acceptable for use are drinking water, demineralized water or a mixture (60/40) of water and glycol. In a closed circulation system, the values in Table 2-3are recommended reference values. To avoid electrochemical corrosion, Eaton recommends adding an inhibitor (e.g. Ferrolix 332/Henkel or Cortec VpCI-649) in the cooling agent.

Note: If no heat-exchanger is used, actions must be taken to avoid electrochemical corrosion. Specifically no brass or copper elements may be used in the liquid circulation of the drive.

Drinking Water Specification

Table 2-3provides general guidelines for water quality.

Note: 1 mg/L = 1 ppm.

Table 2-3: Drinking Water Chemical Specification

Quality

Unit

Value

 

 

 

Acrylamide

µg/L

0.10

 

 

 

Antimony

µg/L

5.0

Arsenic

µg/L

10

 

 

 

Benzene

µg/L

1.0

 

 

 

Benzopyrene

µg/L

0.010

Boron

mg/L

1.0

 

 

 

Bromate

µg/L

10

 

 

 

Cadmium

µg/L

5.0

Chromium

µg/L

50

 

 

 

Copper

mg/L

2.0

 

 

 

Cyanides

µg/L

50

 

 

 

1,2-Dichloroethane

µg/L

3.0

 

 

 

Epichlorohydrin

µg/L

0.10

Fluoride

mg/L

1.5

 

 

 

Lead

µg/L

10

 

 

 

Quality

Unit

Value

 

 

 

Mercury

µg/L

1.0

 

 

 

Nickel

µg/L

20

Nitrate [NO3]

mg/L

50

Nitrate-Nitrogen [NO3-N]

mg/L

11.0

Nitrite [NO2]

mg/L

0.5

Nitrite-Nitrogen [NO2-N]

mg/L

0.15

Bactericides

µg/L

0.10

 

 

 

Bactericides, total

µg/L

0.50

Polynuclear aromatic

µg/L

0.10

hydrocarbons

 

 

Selenium

µg/L

10

 

 

 

Tetrachloroethylene and

µg/L

10

trichloroethylene total

 

 

 

 

 

Trihalomethanes total

µg/L

100

 

 

 

Vinyl chloride

µg/L

0.50

Chlorophenols total

µg/L

10

 

 

 

Table 2-4: Drinking Water Quality

Recommendations — Maximum Values

 

 

Max.

Quality

Unit

Value

 

 

 

 

 

 

Aluminum

µg/L

200

 

 

 

Ammonium [NH2]

mg/L

0.50

Ammonium [NH2-N]

mg/L

0.40

Chloride

mg/L

<100

 

 

 

Manganese

µg/L

50

Iron

µg/L

<0.5

 

 

 

Sulphate

mg/L

250

 

 

 

Sodium

mg/L

200

Oxidizability [CODMn-O2]

mg/L

5.0

No aggressive water allowed.

 

 

To avoid corrosion of piping, the sulphate content must not exceed 150 mg/L.

2-8

For more information visit: www.EatonElectrical.com

MN04005001E

Page 30
Image 30
J. T. Eaton LCX9000 user manual Cooling, Drinking Water Specification, 3 Drinking Water Chemical Specification