Installation of Flow Switch

LCX9000 Liquid-Cooled Drives User Manual

January 2007

Installation of Flow Switch

As stated on Page 2-10, Eaton recommends the installation of the flow supervision in the liquid cooling system. If requested, Eaton delivers the flow switch as an option. The application of the flow switch as well as notes concerning its installation are given below.

About Flow Switch Installation

Eaton recommends mounting the flow switch on the inflow side of the system (see Figure 2-10. Pay attention to the direction of flow. The switch reaches the highest accuracy when it is mounted in horizontal position. If mounted vertically, the mechanical sensor is affected by the Earth’s gravity which reduces the accuracy according to the data given in Table 2-13.

Figure 2-17: Flow Switch: Hose Connection, Fast Connector (Electrical),

Fast Connector Lock Screw, Cable Seal and Clamp

Table 2-13: Flow Switch Data

Description

Specification

 

 

 

 

Hose Connection

G1/2” female, internal thread ISO228-1

 

 

Closing

The switch closes if the flow exceeds 5.3 GPM

 

 

Switching Accuracy:

 

Horizontal installation

-5 – +15% (5.0 – 6.1 GPM)

Vertical Installation

±5% (5.0 – 5.5 GPM)

 

 