J. T. Eaton LCX9000 user manual 2 Cable Sizes 400 - 500V Continued, Units with 6-pulse supply

Models: LCX9000

1 128
Download 128 pages 41.65 Kb
Page 49
Image 49
Table 3-2: Cable Sizes 400 – 500V (Continued)

LCX9000 Liquid-Cooled Drives User Manual

January 2007

Table 3-2: Cable Sizes 400 – 500V (Continued)

 

 

 

Mains and

Terminal Cable Size

 

 

 

 

 

 

 

 

Catalog

 

Motor Cable

Main Terminal

Ground Terminal

Max. Number of

Chassis

Number

Ith

Cu (mm2)

(mm2), Max.

(mm2)

Cables/Bolt Size

 

 

 

 

 

 

 

CH63

LCX820A0-4

820

3x(3x185+95)

 

 

8/M12

 

 

 

 

 

 

 

 

LCX920A0-4

920

4x(3x185+95)

 

 

8/M12

 

 

 

 

 

 

 

 

LCXH10A0-4

1030

4x(3x185+95)

 

 

8/M12

 

 

 

 

 

 

 

CH64

LCXH13A0-4

1370

5x(3x185+95)

 

 

8/M12

 

 

 

 

 

 

 

 

LCXH16A0-4

1640

6x(3x185+95)

 

 

8/M12

 

 

 

 

 

 

 

 

LCXH20A0-4

2060

7x(3x185+95)

 

 

8/M12

 

 

 

 

 

 

 

 

LCXH23A0-4

2300

8x(3x185+95)

 

 

8/M12

 

 

 

 

 

 

 

CH74

LCXH13A0-4

1370

5x(3x185+95)

 

 

4/M12

 

 

 

 

 

 

 

 

LCXH16A0-4

1640

6x(3x185+95)

 

 

4/M12

 

 

 

 

 

 

 

 

LCXH20A0-4

2060

7x(3x185+95)

 

 

4/M12

 

 

 

 

 

 

 

 

LCXH23A0-4

2300

8x(3x185+95)

 

 

4/M12

 

 

 

 

 

 

 

Due to insufficient number of terminal bolt connections for required number of cables, the cabinet must be equipped with an external flexible cable connection block at both mains and motor ends if stiff cable type is used. See also Page 3-7, Step 5. Number of bolt connections = 4.

Three grounding terminals per mounting plate, see Page 3-10.

Units with 6-pulse supply:

Note that all other sizes have three input terminals except for size CH74, which has nine input terminals.

Units with 12-pulse supply:

12-pulse supply can be used with drives of sizes CH72 and CH74. The number of input terminals for both is six.

If 12-pulse supply is used, also consider the fuse selection, see Pages 3-5and 3-6.

MN04005001E

For more information visit: www.EatonElectrical.com

3-3

Page 49
Image 49
J. T. Eaton LCX9000 user manual 2 Cable Sizes 400 - 500V Continued, Units with 6-pulse supply, Units with 12-pulse supply