Control Cables

LCX9000 Liquid-Cooled Drives User Manual

January 2007

Control Cables

The control cables should be at least 20 AWG (.5 mm2) screened multicore cables, see Table 3-1. The maximum terminal wire size is 14 AWG (2.5 mm2) for the relay terminals and 16 AWG (1.5 mm2) for other terminals.

Galvanic Isolation Barriers

The control connections are isolated from the mains potential and the GND terminals are permanently connected to ground. See Figure 4-9.

The digital inputs are galvanically isolated from the I/O ground. The relay outputs are additionally double-isolated from each other at 300V AC (EN-50178).

+10Vref

 

Gate Drivers

L1

L2

L3

GND

 

 

 

 

 

+24V

Control I/O

 

 

 

 

GND

Ground

 

 

 

 

AI1

 

 

 

 

 

AI2+

 

 

 

 

 

AI2-

 

Control

 

 

 

DIN1...

 

 

 

 

Digital Input

Panel

 

 

 

DIN3

 

 

 

 

Group A

 

 

 

 

CMA

 

 

 

 

 

 

 

 

 

DIN4...

Digital Input

 

 

 

 

DIN6

 

Power

 

Group A

 

 

CMB

 

Control

Board

 

AO1+

Analog

 

 

 

Board

 

 

 

AO2-

Output

 

 

 

 

DO1

Digital

 

 

 

 

Output

 

 

 

 

 

 

 

 

 

RO1/1

 

 

 

 

 

RO1/2

 

 

 

 

 

RO1/3

 

 

 

 

 

RO2/1

 

 

 

 

 

RO2/2

 

 

 

 

 

RO2/3

 

 

U

V

W

 

 

 

TI1+

 

 

 

 

 

TI1–

 

 

 

 

 

Figure 4-9: Galvanic Isolation Barriers

4-6

For more information visit: www.EatonElectrical.com

MN04005001E

Page 64
Image 64
J. T. Eaton LCX9000 user manual Control Cables, 9 Galvanic Isolation Barriers