2. Installation
2.Installation
2.1Installation precautions
CAUTION
Handle the inverter with care to prevent damage to the plastic components. Do not hold the inverter by the front cover. It may fall off.
Install the inverter in a place where it is immune to vibration (5.9 m/s2 or less). The inverter is under great influence of ambient temperature.
Install in a location where temperature is within the permissible range
Temperature is 50°C. Models
Ambient 40°C. (UL 508C)
`
5cm5cm
5cm
<Ambient Temp Checking Location>
The inverter will be very hot during operation. Install it on a
Mount the inverter on a flat, vertical and level surface. Inverter orientation must be vertical (top up) for proper heat dissipation. Also leave sufficient clearances around the inverter.
5cm Min
10cm Min
5cm Min
10cm Min
Leave space enough to allow cooled air flowing easily between wiring duct and the unit
Cooling air
Ventilating fan
Protect from moisture and direct sunlight.
Do not install the inverter in any environment where it is exposed to waterdrops, oil mist, dust, etc. Install the inverter in a clean place or inside a “totally enclosed” panel which does not accept any suspended matter.