9. Basic functions

User V/F pattern

 

Group

 

 

LED

 

 

Parametername

 

 

Set

 

 

Min/Max

 

 

Factory

 

 

Unit

 

 

 

 

display

 

 

 

 

value

 

 

range

 

 

defaults

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Function

 

 

F30

 

 

[V/F pattern]

 

 

2

 

0/2

 

0

 

 

 

 

 

group 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F31

 

 

[User V/F frequency 1]

 

-

 

0/400

 

15.0

 

 

Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

~

 

~

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F38

 

 

[User V/F voltage 4]

 

-

 

0/100

 

100

 

%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Select F30 to 2 {User V/F}.

User can adjust the Volt/Frequency ratio according to V/F pattern of specialized motors and load characteristics.

Linear CAUTION

In case of using a standard induction motor, if this value is set much higher than linear V/F pattern, it could result in torque shortage or motor overheating due to over-energizing.

When User V/F pattern is active, F28 - [Torque Boost in forward direction] and F29 - [Torque Boost in reverse direction] are deactivated.

Voltage

 

 

 

 

 

100%

 

 

 

 

 

F38

 

 

 

 

 

F36

 

 

 

 

 

F34

 

 

Linear

 

 

 

 

V/F

 

F32

 

 

 

 

 

 

 

 

 

 

Freq.

Start

F31

F33

F35

F37

Base

freq.

 

 

 

 

freq.

Output voltage adjustment

 

Group

 

 

LED Display

 

 

Parameter Name

 

 

Set

 

 

Min/Max

 

 

Factory

 

 

Unit

 

 

 

 

 

 

 

 

Value

 

 

Range

 

 

Defaults

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Function

 

 

F39

 

 

[Output voltage

 

 

-

 

40/110

 

100

 

%

 

 

group 1

 

 

 

 

adjustment]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This function is used to adjust the output voltage of the inverter. This is useful when you use a motor that has

a rated voltage lower than the input voltage.

Voltage

100% setting

100%

70% setting

70%

Freq.

Base freq.