LG Electronics SV-iC5 Series manual Advanced functions

Models: SV-iC5 Series

1 141
Download 141 pages 11.63 Kb
Page 90
Image 90
Manual background

10. Advanced functions

Starting DC brake

 

Group

 

 

LED Display

 

 

Parameter Name

 

 

Set

 

 

Min/Max

 

 

Factory

 

 

Unit

 

 

 

 

 

 

 

 

value

 

 

Range

 

 

Defaults

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Function

 

 

F12

 

 

[DC Brake start voltage]

 

 

-

 

0/200

 

50

 

%

 

 

group 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F13

 

 

[DC Brake start time]

 

 

-

 

0/60

 

0

 

 

sec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F12 : It sets the level as a percent of H33 – [Motor rated current].

F13 : Motor accelerates after DC voltage is applied for the set time.

Caution :

If excessive DC Brake voltage is set or DC Brake time is set too long, it may cause motor overheating and damage to the motor.

Freq.

 

F13

t

Voltage

F12

Run

 

command

 

Setting F12 or F13 to 0 will disable Starting DC brake.

t : After F13 - [DC Brake start time], the frequency is increasing after DC voltage is applied until the time t. In this case, DC Brake start time may be longer than the set value.

DC brake at a stop

 

Group

 

 

LED Display

 

 

Parameter Name

 

 

 

Set

 

 

Min/Max

 

 

Factory

 

 

Unit

 

 

 

 

 

 

 

 

 

value

 

 

Range

 

 

Defaults

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Function

 

 

F12

 

 

[DC Brake start voltage]

 

 

-

 

0/200

 

50

 

%

 

 

group 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I/O group

 

 

I22

 

 

[Multi-function

input

 

 

11

 

0/24

 

2

 

 

 

 

 

 

 

 

 

 

terminal P3 define]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F12 : Set as a percent of H33 – [Motor rated current].

Select a terminal to issue a command of DC brake during stop among P1 thru P5.

If P3 terminal is set for this function, set 22 to 11 {DC brake during stop}.

Caution :

If excessive DC Brake voltage is set or DC Brake time is set too long, it may cause motor overheating and damage to the motor.

10-2

SV-iC5

Page 90