12. Protective functions
Overload trip
| Group |
|
| LED Display |
|
| Parameter Name |
|
| Set |
|
| Min/Max |
|
| Factory |
|
| Unit |
|
|
|
|
|
|
|
| value |
|
| setting |
|
| default |
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Function |
|
| F56 |
|
| [Overload trip select] |
|
| 1 |
| 0/1 |
| 0 |
|
|
|
| ||
| group 1 |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| F57 |
|
| [Overload trip level] |
| - |
| 30/200 |
| 180 |
| % |
| ||||
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| F58 |
|
| [Overload trip time] |
| - |
| 0/60 |
| 60 |
|
| sec |
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Set F56 to 1.
Inverter output is turned off when motor is overloaded.
Inverter output is turned off when excessive current flows to the motor for F58 – [Overload trip time].
12.3 Stall prevention
| Group |
|
| LED Display |
|
| Parameter Name |
|
| Set |
|
| Min/Max |
|
| Factory |
|
| Unit |
| |
|
|
|
|
|
|
| value |
|
| setting |
|
| default |
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Function |
|
| F59 |
|
| [Stall prevention select] |
|
| - |
| 0/7 |
| 3 |
|
|
|
| |||
| group 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| F60 |
|
| [Stall prevention level] |
|
| - |
| 30/150 |
| 150 |
| % |
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| I/O group |
|
| I54 |
|
| output |
| 7 |
| 0/17 |
| 12 |
|
|
|
| ||||
|
|
|
|
|
| terminal select] |
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| I55 |
|
|
| 7 |
|
|
|
| 17 |
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
During acceleration : Motor acceleration is stopped when current exceeding the value set in F60 flows.
During constant run : Motor decelerates when current exceeding the value set in F60 flows.
During deceleration : Motor deceleration is stopped when inverter DC link voltage rises above a certain voltage level.
F60 : The value is set as the percent of motor rated current (H33).
I54, I55: Inverter outputs signals through
F59 : Stall prevention can be set as the table below.
F59 | [Stall prevention | Setting | During | During constant | During |
| select] | Deceleration | speed | Acceleration | |
|
|
| Bit 2 | Bit 1 | Bit 0 |
|
|
|
|
|
|
|
| 0 | - | - | - |
|
|
|
|
|
|
|
| 1 | - | - |
|
|
|
|
|
|
|
|
| 2 | - |
| - |
|
|
|
|
|
|
|
| 3 | - |
|
|
|
|
|
|
|
|
|
| 4 |
| - | - |
|
|
|
|
|
|
|
| 5 |
| - |
|
|
|
|
|
|
|
|
| 6 |
|
| - |
|
|
|
|
|
|
|
| 7 |
|
|
|
|
|
|
|
|
|