12. Protective functions

Overload trip

 

Group

 

 

LED Display

 

 

Parameter Name

 

 

Set

 

 

Min/Max

 

 

Factory

 

 

Unit

 

 

 

 

 

 

 

 

value

 

 

setting

 

 

default

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Function

 

 

F56

 

 

[Overload trip select]

 

 

1

 

0/1

 

0

 

 

 

 

 

group 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F57

 

 

[Overload trip level]

 

-

 

30/200

 

180

 

%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F58

 

 

[Overload trip time]

 

-

 

0/60

 

60

 

 

sec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set F56 to 1.

Inverter output is turned off when motor is overloaded.

Inverter output is turned off when excessive current flows to the motor for F58 – [Overload trip time].

12.3 Stall prevention

 

Group

 

 

LED Display

 

 

Parameter Name

 

 

Set

 

 

Min/Max

 

 

Factory

 

 

Unit

 

 

 

 

 

 

 

 

value

 

 

setting

 

 

default

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Function

 

 

F59

 

 

[Stall prevention select]

 

 

-

 

0/7

 

3

 

 

 

 

 

group 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F60

 

 

[Stall prevention level]

 

 

-

 

30/150

 

150

 

%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I/O group

 

 

I54

 

 

[Multi-function

output

 

7

 

0/17

 

12

 

 

 

 

 

 

 

 

 

 

terminal select]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I55

 

 

[Multi-function relay select]

 

7

 

 

 

 

17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

During acceleration : Motor acceleration is stopped when current exceeding the value set in F60 flows.

During constant run : Motor decelerates when current exceeding the value set in F60 flows.

During deceleration : Motor deceleration is stopped when inverter DC link voltage rises above a certain voltage level.

F60 : The value is set as the percent of motor rated current (H33).

I54, I55: Inverter outputs signals through multi-function output terminal (MO) or relay output (30AC) when stall prevention function is activated. Stall prevention operation can be monitored by external sequence.

F59 : Stall prevention can be set as the table below.

F59

[Stall prevention

Setting

During

During constant

During

 

select]

Deceleration

speed

Acceleration

 

 

 

Bit 2

Bit 1

Bit 0

 

 

 

 

 

 

 

 

0

-

-

-

 

 

 

 

 

 

 

 

1

-

-

 

 

 

 

 

 

 

 

 

2

-

 

-

 

 

 

 

 

 

 

 

3

-

 

 

 

 

 

 

 

 

 

 

4

 

-

-

 

 

 

 

 

 

 

 

5

 

-

 

 

 

 

 

 

 

 

 

6

 

 

-

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

12-3

SV-iC5

Page 121
Image 121