3. Wiring
WARNING
Use the Type 3 grounding method (Ground impedance: Below 100ohm). Use the dedicated ground terminal to ground the inverter. Do not use the screw in the case or chassis, etc for grounding.
Dedicated | Ground | Dedicated | Ground |
Terminal |
| Terminal |
|
☞Note : Remove front and bottom cover before starting grounding.
☞Caution : Follow the specifications below when grounding the inverter.
| Model |
| 004iC5, 008iC5 – 1,1F | 015iC5, 022iC5 – 1,1F |
|
|
|
|
|
| Wire size |
| 2mm2 | 2mm2 |
| Lug |
| 2mm2, 3φ | 2mm2, 3φ |
| Ground |
| Below 100 ohm | Below 100 ohm |
| impedance |
| ||
|
|
|
| |
|
|
|
|
|