7. Function list
Function group 2
| LED |
|
| Parameter |
|
| Min/Max |
|
|
|
| Description |
|
| Factory |
|
| Adjustable |
|
| Page |
| ||
| display |
|
| Name |
|
| Range |
|
|
|
|
|
| defaults |
|
| during run |
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
| H26 |
|
| [Number of |
| 0/10 |
|
| This parameter sets the number of | 0 |
|
| O |
| 10- |
| ||||||||
|
|
|
| Auto Restart |
|
|
|
|
| restart tries after a fault occurs. |
|
|
|
|
|
| 15 |
| ||||||
|
|
|
| try] |
|
|
|
|
| Auto Restart is deactivated if the fault |
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| outnumbers the restart tries. |
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| This function is active when [drv] is set |
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| to 1 or 2 {Run/Stop via control terminal}. |
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| Deactivated | during | active protection |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| function (OHT, LVT, EXT, HWT etc.) |
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
| H27 |
|
| [Auto Restart |
|
| 0/60 [sec] |
|
| This parameter sets the time between | 1.0 |
|
| O |
|
|
|
| ||||||
|
|
|
| time] |
|
|
|
|
| restart tries. |
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| H30 |
|
| [Motor type |
| 0.2/2.2 |
| 0.2 |
| 0.2 kW |
|
|
| - |
|
| X |
|
| |||||
|
|
|
|
|
|
|
|
| 1) |
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| select] |
|
|
|
| 0.4 |
| 0.4 kW |
|
|
| Automatically |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| set |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 0.75 |
| 0.75 kW |
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| 1.5 |
| 1.5 kW |
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| 2.2 |
| 2.2 kW |
|
|
|
|
|
|
|
|
|
|
| ||
| H31 |
|
| [Number of |
| 2/12 |
|
| This setting is displayed via rPM in | - |
|
| X |
|
|
|
| |||||||
|
|
|
| motor poles] |
|
|
|
|
| drive group. |
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| H32 |
|
| [Rated slip |
| 0/10 |
|
|
|
| rpm ⋅ P | |
| - |
|
| X |
|
|
|
| |||
|
|
|
|
|
|
|
|
| 2) |
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
| f s | = f r − |
| |
|
|
|
|
|
|
|
| |||
|
|
|
| frequency] |
|
| [Hz] |
|
| 120 |
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
| | |
| Automatically |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| fs = Rated slip frequency |
| set |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| Where, |
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
| f r = Rated frequency |
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| rpm = Motor nameplate RPM |
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| P = Number of Motor poles |
|
|
|
|
|
|
|
|
| ||||
| H33 |
|
| [Motor rated |
| 1.0/20 |
|
| Enter motor rated current on the |
| - |
|
| X |
|
|
|
| ||||||
|
|
|
| current] |
|
| [A] |
|
| nameplate. |
|
|
|
|
|
|
|
|
|
|
|
| ||
| H34 |
|
| [No Load |
| 0.1/12 |
|
| Enter the current value detected when |
| - |
|
| X |
|
| ||||||||
|
|
|
| Motor |
|
| [A] |
|
| the motor is rotating in rated rpm after the |
|
|
|
|
|
|
|
|
| |||||
|
|
|
| Current] |
|
|
|
|
| load connected to the motor shaft is |
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| removed. |
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| Enter the 50% of the rated current |
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| value when it is difficult to measure H34 - |
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| [No Load Motor Current]. |
|
|
|
|
|
|
|
|
| |||||
| H36 |
|
| [Motor |
| 50/100 |
|
| Enter the motor efficiency (see motor |
| - |
|
| X |
|
|
|
| ||||||
|
|
|
| efficiency] |
| [%] |
|
| nameplate). |
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|