9. Basic functions
More precise time unit can be set corresponding to load characteristics as shown below.
Code | Parameter Name | Setting range | Set | Description |
|
| value | ||
|
|
|
| |
|
|
|
|
|
H71 | [Accel/Decel Time setting | 0.01~600.00 | 0 | Unit: 0.01 sec. |
|
|
|
| |
| 0.1~6000.0 | 1 | Unit: 0.1 sec. | |
| unit] | |||
|
|
|
| |
| 1~60000 | 2 | Unit: 1 sec. | |
|
| |||
|
|
|
|
|
Accel/Decel time based on Run frequency
| Group |
|
| LED display |
|
| Parameter name |
|
| Set |
|
| Min/Max |
|
| Factory |
|
| Unit |
|
|
|
|
|
|
|
| value |
|
| range |
|
| defaults |
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| Drive |
|
| ACC |
|
| [Accel time] |
| - |
| 0/6000 |
| 5.0 |
|
| sec |
| |||
| group |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
| dEC |
|
| [Decel time] |
| - |
| 0/6000 |
| 10.0 |
|
| sec |
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| Function |
|
| H70 |
|
| [Frequency reference | for |
| 1 |
| 0/1 |
| 0 |
|
|
|
| ||
| group 2 |
|
|
|
| Accel/Decel] |
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Accel/Decel time is set at the ACC/dEC.
If you set H70 to 1 {Delta frequency}, Accel/Decel time is the time that takes to reach a target freq from run freq (Currently operating freq.).
When H70 and Accel time are set to 1 {Delta frequency} and 5 sec, respectively,
(A zone: run freq 10 Hz applied first, B zone: Operating via 10 Hz, different run freq is not issued
C:30Hz Run freq (in this case, Target freq) issued while 10 Hz run freq is applied. But the preset accel time 5 sec is maintained. )
Freq. |
|
| 30Hz |
|
| (Target freq.) | |
command |
|
| |
(Run freq.) | (Delta freq.) | ||
10Hz | |||
A | B | C | Time |
5 | 7 | 12 | [sec] |
Run |
|
|
|
command |
|
|
|
5 sec |
| 5 sec |
|
|