TROUBLESHOOTING | ||
| Observe all Safety Guidelines detailed throughout this manual |
|
PROBLEMS
(SYMPTOMS)
POSSIBLE
CAUSE
RECOMMENDED
COURSE OF ACTION
Device goes off line during welding. | 1. Interference / Noise. | 1. Verify that DeviceNet cables are not | |
|
|
| running next to (in close proximity |
|
|
| with) current carrying conductors. |
|
|
| This includes the welding cables, input |
|
|
| cables, etc. |
|
| 2. Termination. | 2. Verify that the DeviceNet bus is termi- |
|
|
| nated correctly. |
|
| 3. Shielding. | 3. Verify that the cable shielding is cor- |
|
|
| rectly grounded at the bus power sup- |
|
|
| ply. The shield should be tied into the |
|
|
| bus ground at only one point. |
|
| 4. Power Supply. | 4. Verify that the DeviceNet bus power |
|
|
| supply can supply sufficient current for |
|
|
| the devices on the network. |
|
|
|
|
|
| 5. Expected Packet Rate. | 5. Verify that 1000/(Expected Packet |
|
|
| Rate) ≤ (scans per second). The |
|
|
| DeviceNet tab of the Diagnostics |
|
|
| Utility displays these values. |
|
|
|
|
Output will not come on. | 1. DeviceNet trigger not asserted. | 1. From the DeviceNet tab of the | |
|
|
| Diagnostics Utility, select Monitor. The |
|
|
| Monitor window will be displayed. Verify |
|
|
| under the “Produced Assembly” that |
|
|
| “Trigger” is highlighted. |
|
| 2. Touch Sense command. | 2. From the DeviceNet tab of the |
|
|
| Diagnostics Utility, select Monitor. The |
|
|
| Monitor window will be displayed. Verify |
|
|
| under the “Produced Assembly” that |
|
|
| “Touch Sense” is NOT highlighted. |
|
| 3. Passive Mode. | 3. The DeviceNet tab of the Diagnostics |
|
|
| Utility displays the POWER WAVE®ʼs |
|
|
| passive mode status. If the status |
|
|
| needs to be changed, select Configure, |
|
|
| and make the necessary modification. |
|
|
|
|
|
| 4. Welding Cables. | 4. Verify that welding cables are connect- |
|
|
| ed properly. |
|
| 5. Output Disabled | 5. From the DeviceNet tab of the |
|
|
| Diagnostics Utility, select Monitor. The |
|
|
| Monitor window will be displayed. Verify |
|
|
| under the “Produced Assembly” that |
|
|
| “Disable Output” is NOT highlighted. |
|
|
|
|
CAUTION
If for any reason you do not understand the test procedures or are unable to perform the tests/repairs safely, contact your Local Lincoln Authorized Field Service Facility for technical troubleshooting assistance before you proceed.
POWER WAVE® i400