Lincoln Electric IM986 manual E-12, Troubleshooting, Problems Symptoms, Possible Cause

Models: IM986

1 57
Download 57 pages 27.18 Kb
Page 49
Image 49
E-12

E-12

TROUBLESHOOTING

E-12

 

Observe all Safety Guidelines detailed throughout this manual

 

PROBLEMS

(SYMPTOMS)

POSSIBLE

CAUSE

RECOMMENDED

COURSE OF ACTION

Analog Inputs donʼt respond or donʼt

1.

Analog Scans Between Updates.

1.

The DeviceNet tab of the Diagnostics

respond quickly.

 

 

 

Utility displays the POWER WAVE®ʼs

 

 

 

 

“Analog Scans Between Updates” and

 

 

 

 

“I/O Scans/Sec.” Verify that “Analog

 

 

 

 

Scans Between Updates” is ¼ of “I/O

 

 

 

 

Scans/Sec” value.

 

2.

Analog In Active Selections.

2.

From the DeviceNet tab of the

 

 

 

 

Diagnostics Utility, select Configure.

 

 

 

 

Verify in “Analog Input Channels” that

 

 

 

 

the required channels are set active.

 

 

 

 

 

 

3.

Analog Hysteresis.

3.

From the DeviceNet tab of the

 

 

 

 

Diagnostics Utility, select Configure.

 

 

 

 

Verify in “Analog Input Channels” that

 

 

 

 

the Hysteresis settings are all 0.

 

4.

Passive Mode.

4.

The DeviceNet tab of the Diagnostics

 

 

 

 

Utility displays the POWER WAVE®ʼs

 

 

 

 

passive mode status. If the status

 

 

 

 

needs to be changed, select

 

 

 

 

Configure, and make the necessary

 

 

 

 

modification.

Gas purge not working.

1.

Out of gas.

1.

Verify there is gas available at the

 

 

 

 

input of the gas solenoid.

 

 

 

 

 

 

2.

Gas Purge not asserted.

2.

From the DeviceNet tab of the

 

 

 

 

Diagnostics Utility, select Monitor. The

 

 

 

 

Monitor window will be displayed.

 

 

 

 

Verify under the “Produced Assembly”

 

 

 

 

that “Gas Purge” is highlighted.

 

 

 

 

 

 

3.

Passive Mode.

3.

The DeviceNet tab of the Diagnostics

 

 

 

 

Utility displays the POWER WAVE®ʼs

 

 

 

 

passive mode status. If the status

 

 

 

 

needs to be changed, select

 

 

 

 

Configure, and make the necessary

 

 

 

 

modification.

 

4.

Gas Lines.

4.

Verify nothing is obstructing the flow

 

 

 

 

of gas.

 

 

 

 

 

Manual backgroundManual background CAUTION

If for any reason you do not understand the test procedures or are unable to perform the tests/repairs safely, contact your Local Lincoln Authorized Field Service Facility for technical troubleshooting assistance before you proceed.

POWER WAVE® i400

Page 49
Image 49
Lincoln Electric IM986 manual E-12, Troubleshooting, Problems Symptoms, Possible Cause, Recommended Course Of Action