Group-l Code Assignment—ANI Start
Specifies the code used to indicate the beginning of an ANI number.
Value Range
Undefined, 1–15
Maintenance Console Location
3.40 [1-1] Slot—Card Property - E1 type—MFC-R2 Setting 1
Programming Manual References
None
Feature Guide References
None
Group-l Code Assignment—ANI Complete (1)–(4)
Specifies the code used to indicate the end of an ANI number.
Value Range
ANI Complete (1): 1–15
ANI Complete (2)–(4): Undefined, 1–15
Maintenance Console Location
3.40 [1-1] Slot—Card Property - E1 type—MFC-R2 Setting 1
Programming Manual References
None
Feature Guide References
None
Group-l Code Assignment—ANI Reject
Specifies the code used to reject an ANI number.
Value Range
1–15
Maintenance Console Location
3.40 [1-1] Slot—Card Property - E1 type—MFC-R2 Setting 1
352 PC Programming Manual