Panasonic WJ-FS616C manual Camera Site Alarm, Video Loss Alarm, Camera Switching Pulse Loss Alarm

Models: WJ-FS616C

1 82
Download 82 pages 55.13 Kb
Page 27
Image 27

Camera Site Alarm

This item lets you enable or disable the camera site alarm function.

1.Move the cursor to the CAM SITE ALM parameter by pressing the C or D button.

2Select ON or OFF by pressing the A or B button.

ON: Enables camera site alarm function.

OFF: Disables camera site alarm function.

The factory default setting is OFF.

Note: To use this function, the WV-PB6164 Data Multiplex Boards must be installed in the video mul- tiplexer.

Video Loss Alarm

This item lets you enable or disable the alarm function when the camera video signal is lost.

1.Move the cursor to the VIDEO LOSS ALM parameter.

2Select either ON or OFF.

ON: Enables alarm function when video loss is detect- ed.

OFF: Disables alarm function when video loss is detect- ed.

The factory default setting is ON.

Camera Switching Pulse Loss Alarm

This item lets you enable or disable alarm display (SW LOSS) on the monitor screen when the camera switching pulse is lost.

1.Move the cursor to the SW-LOSS ALM parameter.

2.Select either ON or OFF.

ON: Enables alarm display on the monitor screen.

OFF: Disables alarm display on the monitor screen.

The factory default setting is OFF.

Alarm Display on the Monitors

This item lets you enable or disable alarm display on the spot and multiscreen monitors.

1.Move the cursor to the ALM DISPLAY parameter.

2.Select either ON or OFF.

ON: Enables alarm display on the Monitors.

OFF: Disables alarm display on the Monitors.

The factory default setting is ON.

Alarm Output Duration

This item lets you select the output duration of the alarm signal from the ALARM/REMOTE port.

The alarm is automatically reset after the programmed duration has passed.

1.Move the cursor to the ALM OUTPUT DUR parameter.

2.Select the desired duration.

1SEC - 5MIN: Selects an alarm duration between 1 second and 5 minutes.

EXT: Alarm output continues until the ALARM RESET button is pressed or the external alarm recover sig- nal is received from the ALARM/REMOTE port.

The factory default setting is 2 SEC.

Alarm Buzzer Duration

This item lets you select the ringing duration of the built-in alarm buzzer when an alarm is activated.

1.Move the cursor to the ALM BUZZER DUR parameter.

2.Select the desired duration.

OFF: Disables alarm buzzer, regardless of an incoming alarm.

1SEC - 5 MIN: Selects buzzer duration between 1 sec- ond and 5 minutes.

EXT: Alarm buzzer continues to beep until the ALARM RESET button is pressed or the external alarm recover signal is received from the ALARM/ REMOTE port.

The factory default setting is 2 SEC.

27

Page 27
Image 27
Panasonic WJ-FS616C Camera Site Alarm, Video Loss Alarm, Camera Switching Pulse Loss Alarm, Alarm Display on the Monitors