Chapter 6 Command Reference 109
If the DMTIP value exceeds the drive’s maximum output current (TDIMAX),
the DMTIP value will be ignored and the maximum allowable value will be
used (see Table 45). The drive reports EØ–Motor Configuration
Warning and E12–Peak Current Too High.
Maximum Current Rating (RMS)
AR-01xx 3A
AR-02xx 5.25A
AR-04xx 9A
AR-08xx 13.5A
AR-13xx 14.1
AR-20xE 30
AR-30xE 48
Table 45 Peak Current Rating for Aries Drives
DMTJ Motor Rotor Inertia / Forcer Mass
Type Motor Product Rev
Syntax <a_><!>DMTJ<r> (does not take effect until RESET or
cycle power)
Aries 2.0
Units Rotary motor: r = kgm2 * 1Ø-6
Linear motor: r = kg
Range Rotary motor: Ø.ØØØ to 1ØØØØØØ.ØØØ : ±Ø.ØØ1
Linear motor: DMEPIT (electrical pitch) dependent
Default Ø.ØØØ (DMTJ of Ø results in motor config. error)
Response DMTJ: *DMTJ2ØØ.6ØØ
See Also DMTR, CONFIG
Note: This command does not take effect until you cycle power to the drive,
or send the RESET command.
Auto-Setup: When using a Parker motor and the Aries Support Tool, this
command is automatically set for the selected motor.
If you did not use the Aries Support Tool, are using non-Parker motors, or
sent an RFS command to the drive, the parameter is set to zero (0)—you
must manually set this parameter to a non-zero number.
If the drive is powered up when this command is set to zero (for instance, if
RFS is executed), the drive reports a motor configuration error with E13, and
shuts down the drive (DRIVEØ).
For a list of auto-configured commands, see DMTR.
The DMTJ command sets the motor rotor inertia for rotary motors, or the
forcer mass for linear motors.