PIPE THE BOILER
b)Temporary low temperature operation is acceptable within limits. For occasional cold start- ups condensation will occur, but will have limited effects. If the system is frequently allowed to cool to room temperature, such as on night
2.Constant Low Temperature
a)For systems with a relatively constant low operating temperature (such as heat pump systems), you can pipe a fixed flow
3.Variable Low Temperature
a)When the return water temperature from the system will vary (outdoor reset, snow melt, etc.) a
fixed bypass will not work. Fixed bypass piping | Figure 3.3: Fixed | |
works by setting a high temperature rise through | ||
| ||
the boiler. As the system return temperature rises |
| |
(during primary heating months, for example) |
| |
the boiler will cycle on the limit control |
| |
frequently, causing poor performance and |
| |
excessive cycling. To protect the boiler and |
| |
provide proper operation, install a temperature |
|
Figure 3.4: Fixed By-Pass Piping, Multiple Boilers
22