BOILER RATINGS & DIMENSIONS

11. BOILER RATINGS & DIMENSIONS

Table 11.1: Series LC/LCE Boiler Ratings

SERIES LC/LCE BOILER RATINGS

 

Gross

 

I=B=R Burner Capacity

 

I=B=R Net Ratings

 

Combustion Efficiency

Boiler

I=B=R

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

Output

Boiler

Oil

Gas

Steam

 

Steam

 

Water

 

 

Number

Mbh

H.P.

GPH

MBH

Sq. Ft.

 

MBH

 

MBH

Oil

Gas

LC-04

547

16.3

4.75

686

1708

 

410

 

476

83.7

81.2

LC-05R

649

19.4

5.60

808

2029

 

487

 

564

83.7

81.2

LC-05

707

21.1

6.10

881

2208

 

530

 

615

83.7

81.2

LC-06

868

25.7

7.50

1077

2713

 

651

 

755

83.7

81.1

LC-07

1029

30.7

8.80

1273

3217

 

772

 

895

83.6

81.1

LC-08

1189

35.5

10.20

1469

3717

 

892

 

1034

83.6

81.1

LC-09

1350

40.3

11.60

1664

4250

 

1020

 

1174

83.6

81.1

LC-10

1511

45.1

12.80

1860

4804

 

1153

 

1314

83.6

81.1

LC-11

1672

49.9

14.20

2056

5367

 

1288

 

1454

83.6

81.1

LC-12

1832

54.7

15.60

2252

5917

 

1420

 

1593

83.6

81.1

LCE-13

1966

58.7

17.00

2464

6358

 

1526

 

1710

83.5

81.0

LCE-14

2125

63.5

18.40

2657

6875

 

1650

 

1848

83.5

81.0

LCE-15

2284

68.2

19.80

2850

7388

 

1773

 

1986

83.5

81.0

LCE-16

2444

73.0

21.00

3043

7908

 

1898

 

2125

83.5

81.0

LCE-17

2603

77.8

22.50

3236

8421

 

2021

 

2263

83.5

81.0

LCE-18

2763

82.5

24.00

3429

8938

 

2145

 

2403

83.5

81.0

LCE-19

2922

87.3

25.00

3622

9454

 

2269

 

2541

83.5

81.0

LCE-20

3082

92.1

26.50

3815

9971

 

2393

 

2680

83.5

81.0

LCE-21

3256

97.3

28.00

4027

10533

 

2528

 

2831

83.6

81.1

LCE-22

3430

102.5

29.50

4239

11096

 

2663

 

2983

83.6

81.1

LCE-23

3604

107.7

31.00

4451

11658

 

2798

 

3134

83.7

81.2

LCE-24

3777

112.8

32.50

4663

12217

 

2932

 

3284

83.7

81.2

 

 

 

 

 

 

 

 

 

 

 

 

1Burner input based on No. 2 fuel oil with a heating value of 140,000 Btu per gallon.

2Net I=B=R water ratings based on an allowance of 1.15.

3Net I=B=R steam ratings based on an allowance for LC-04 to LC-08=1.333, LC-09=1.323, LC-10=1.310, LC-11=1.298, LC-12=1.290, LCE-13 to LCE-24=1.288.

4Consult factory before selecting a boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems, etc.

5Combustion efficiency determined in accordance with The Hydronics Institute’s Testing and Rating Standard for Heating Boilers.

Figure 11.1: Tankless Coil Pressure Drops

42

Page 44
Image 44
PB Heat Gas/Oil Boilers manual Boiler Ratings & Dimensions, Series LC/LCE Boiler Ratings