PIPE THE BOILER

Figure 3.2: LC/LCE Boiler Piping

Table 3.1: Boiler Supply and Return Connections & Recommended Header Sizing

 

I=B=R

GPM

 

Suggested Supply

 

 

Return Connections

 

 

Connections – Top

 

 

 

Rear and Side

 

Model

Gross

 

 

 

 

 

@ 20°F

 

 

 

 

 

 

 

 

 

 

 

Output

Rise

Number

 

Size

 

Header

Number

Size

 

Header

 

MBH

 

 

 

 

 

 

(Inches)

 

(Inches)

(Inches)

 

(Inches)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LC-04

547

55

1

 

2-1/2

 

2-1/2

1

 

2-1/2

 

2-1/2

LC-05R

649

65

1

 

2-1/2

 

2-1/2

1

 

2-1/2

 

2-1/2

LC-05

707

71

1

 

2-1/2

 

2-1/2

1

 

2-1/2

 

2-1/2

LC-06

868

87

1

 

3

 

3

1

 

3

 

3

LC-07

1029

103

1

 

3

 

3

1

 

3

 

3

LC-08

1189

119

2

 

3

 

3

2

 

3

 

3

LC-09

1350

135

2

 

3

 

3

2

 

3

 

3

LC-10

1511

151

2

 

4

 

4

2

 

3

 

4

LC-11

1672

167

2

 

4

 

4

2

 

3

 

4

LC-12

1832

183

2

 

4

 

4

2

 

3

 

4

LCE-13

1966

197

2

 

4

 

4

2

 

3

 

4

LCE-14

2125

213

2

 

4

 

4

2

 

3

 

4

LCE-15

2284

228

2

 

4

 

4

2

 

3

 

4

LCE-16

2444

244

2

 

4

 

4

2

 

3

 

4

LCE-17

2603

260

2

 

4

 

5

2

 

3

 

5

LCE-18

2763

276

2

 

4

 

5

2

 

3

 

5

LCE-19

2922

292

2

 

4

 

5

2

 

3

 

5

LCE-20

3082

308

2

 

4

 

5

2

 

3

 

5

LCE-21

3256

326

2

 

4

 

5

3

 

3

 

5

LCE-22

3430

343

2

 

4

 

5

3

 

3

 

5

LCE-23

3604

360

2

 

4

 

5

3

 

3

 

5

LCE-24

3777

378

2

 

4

 

5

3

 

3

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

21

Page 23
Image 23