CONNECT FUEL PIPING
Table 7.1: Capacity of Gas Supply Pipe in Cubic Feet Per Hour of Natural Gas for Pressure Drop of 0.3 inch Water Column.
Pipe Length | 2" | 3" | 4" | 6" | |||
(Feet) | Pipe | Pipe | Pipe | Pipe | Pipe | Pipe | Pipe |
|
|
|
|
|
|
|
|
10 | 1050 | 1600 | 3050 | 4800 | 8500 | 17500 | 44000 |
|
|
|
|
|
|
|
|
20 | 730 | 1100 | 2100 | 3300 | 5900 | 12000 | 31000 |
|
|
|
|
|
|
|
|
30 | 590 | 890 | 1650 | 2700 | 4700 | 9700 | 25000 |
|
|
|
|
|
|
|
|
40 | 500 | 760 | 1450 | 2300 | 4100 | 8300 | 22000 |
|
|
|
|
|
|
|
|
50 | 440 | 670 | 1270 | 2000 | 3600 | 7400 | 20000 |
|
|
|
|
|
|
|
|
60 | 400 | 610 | 1150 | 1850 | 3250 | 6800 | 18000 |
|
|
|
|
|
|
|
|
70 | 350 | 560 | 1050 | 1700 | 3000 | 6200 | 17000 |
|
|
|
|
|
|
|
|
90 | 320 | 490 | 930 | 1500 | 2600 | 5400 | 15000 |
|
|
|
|
|
|
|
|
100 | 305 | 460 | 870 | 1400 | 2500 | 5100 | 14000 |
|
|
|
|
|
|
|
|
150 | 250 | 380 | 710 | 1130 | 2000 | 4100 | 11500 |
|
|
|
|
|
|
|
|
Above ratings based on natural gas with specific gravity of 0.60 allowing pressure drop of 0.3 inches water column. No allowance is needed for pipe fittings. Use the following multipliers on above capacities for specific gravity other than 0.60:
Specific Gravity | 0.50 | 0.55 | 0.60 | 0.65 | 0.70 |
|
|
|
|
|
|
Multiply Capacity by: | 1.10 | 1.04 | 1.00 | 0.962 | 0.926 |
|
|
|
|
|
|