CONNECT FUEL PIPING

Table 7.1: Capacity of Gas Supply Pipe in Cubic Feet Per Hour of Natural Gas for Pressure Drop of 0.3 inch Water Column.

Pipe Length

1-1/4"

1-1/2"

2"

2-1/2"

3"

4"

6"

(Feet)

Pipe

Pipe

Pipe

Pipe

Pipe

Pipe

Pipe

 

 

 

 

 

 

 

 

10

1050

1600

3050

4800

8500

17500

44000

 

 

 

 

 

 

 

 

20

730

1100

2100

3300

5900

12000

31000

 

 

 

 

 

 

 

 

30

590

890

1650

2700

4700

9700

25000

 

 

 

 

 

 

 

 

40

500

760

1450

2300

4100

8300

22000

 

 

 

 

 

 

 

 

50

440

670

1270

2000

3600

7400

20000

 

 

 

 

 

 

 

 

60

400

610

1150

1850

3250

6800

18000

 

 

 

 

 

 

 

 

70

350

560

1050

1700

3000

6200

17000

 

 

 

 

 

 

 

 

90

320

490

930

1500

2600

5400

15000

 

 

 

 

 

 

 

 

100

305

460

870

1400

2500

5100

14000

 

 

 

 

 

 

 

 

150

250

380

710

1130

2000

4100

11500

 

 

 

 

 

 

 

 

Above ratings based on natural gas with specific gravity of 0.60 allowing pressure drop of 0.3 inches water column. No allowance is needed for pipe fittings. Use the following multipliers on above capacities for specific gravity other than 0.60:

Specific Gravity

0.50

0.55

0.60

0.65

0.70

 

 

 

 

 

 

Multiply Capacity by:

1.10

1.04

1.00

0.962

0.926

 

 

 

 

 

 