4.8 Call Delay

Call Delay is the programmed length of time the Model 1104 waits, following detection of an alarm, before it begins the dial- out sequence. This applies only to the first call. (Delay time between calls is also programmable: refer to Intercall Time,

Section 4-11.)

The purpose for Call Delay is to allow time for personnel at the Model 1104’s installation site to respond to and cancel an alarm before dial-out begins. During this time, the Model 1104 will audibly repeat its “alert condition” message (unless the Local Voice Mute feature has been activated—refer to Section 4.9). The default for Call Delay is 30 seconds. Call Delay can be programmed from 0 seconds to 60 minutes (1 hour).

4.8.1 Programming the Call Delay

To program the Call Delay:

1.Press SET.

SET

#

2.Press CALL DELAY.

1

CALL

DELAY

The Model 1104 will respond: “Enter minutes.”

3.Using the number keys, enter the minutes.

1

CALL

DELAY

4

MAX CALLS

7

RECOGNITION

TIME

2

VOICE

REPS

5

TEMP LIMITS

8

CLOCK

0

ID NUMBER

POWER

3

INTERCALL

TIME

6

CALIBRATE

9

LISTEN TIME

SOUND

The Model 1104 recites the digits as they are pressed.