Sensaphone® Model 1104 User’s Manual

5.6.1Programming Temperature Calibration

1.Press SET.

SET

#

2. Press CALIBRATE.

6

CALIBRATE

3.Press the number (1 to 4) of the selected temperature input to be calibrated.

1

CALL

DELAY

4

MAX CALLS

2

3

VOICE

INTERCALL

REPS

TIME

4.Enter the number required to offset the current temperature reading so a correct reading is obtained.

To program a positive offset number (up to +10 degrees), enter the number on the keypad. The Model 1104 recites the digits as they are pressed.

To program a negative offset number (up to –10 degrees), first press PAUSE. The unit responds with a “beep.” Next, enter the number on the keypad. The unit recites the digits as they are pressed.

5.Press ENTER. The Model 1104 responds:“Enter.”

ENTER

TONE

PM

NOTE

If you find that your calibration offset exceeds more than + 5 or –5 degrees, other complicating factors could be affecting normal operation of the Model 1104. Call Phonetics for technical assistance.

5.6.2Interrogating Temperature Calibration

1.Press WHAT IS.

WHAT

IS

*

2. Press CALIBRATE.

72

Page 72
Image 72
Phonetics 1104 user manual Programming Temperature Calibration, Interrogating Temperature Calibration