7. Press ENTER. The Model 1104 responds: “Enter.”

ENTER

TONE

PM

NOTE

Do not set temperature limits too close to normal room temperature. Minor temperature fluctuations could result in frequent and unnecessary alarm dialouts.

5.4.2Disabling Alarm Response to High or Low Temperature

To disable alarm response to either high or low temperature settings exclusively, enter the maximum temperature limit when programming the selected input. (The Model 1104 will not respond to temperatures encountered at maximum settings or beyond.) Begin by following the key sequence shown in Section 5.4.1, and when prompted to enter the high or low temperature value:

Set high temperature to either +150º F or +65º C (high temperature limit) to prevent the Model 1104 from responding to a high temperature alarm.

Set low temperature to either -20o F or -30o C to prevent the Model 1104 from responding to a low temperature alarm.

5.4.3Interrogating High and Low Temperature Limits

1.Press WHAT IS.

WHAT

IS

*

2. Press TEMP LIMITS.

5

TEMP LIMITS

70