EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 10−1
Chapter 10 Product Specifications

10.1 Model Numbers

The UPS is housed in a free-standing cabinet, divided into two sections with safety
shields behind the door and front panels. The UPS is available in 50 or 60 Hz with
various output power ratings.
Models Power Rating Frequency
Powerware 9395−1100/1000 (four UPM) 1000 kVA 50/60 Hz
Powerware 9395−1100/1100 (four UPM) 1100 kVA 50/60 Hz
Powerware 9395−1100/650 (three UPM) 650 kVA 50/60 Hz
Powerware 9395−1100/750 (three UPM) 750 kVA 50/60 Hz
Powerware 9395−1100/825 (three UPM) 825 kVA 50/60 Hz
The following sections detail the input, output, environmental, and battery
specifications for the UPS.

10.2 Specifications

10.2.1 UPS Input

Operating Input Voltage 480 Vac
Operating Input Frequency Range 50/60 Hz
Operating Input Current See Table 3-4 on page 3−9 or Table 3-5 on page 3−10 for four UPM
models.
See Table 3-6 on page 3−11 or Table 3-7 on page 3−12 for three UPM
models.
Reduced for Generator
Adjustable
Input Current Harmonic Content 5% THD at full load
Power Factor Minimum 0.99
Line Surges 6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4
Battery Voltage 480 Vdc
Battery Charging Capacity Configurable per UPM at nominal line voltage:
Up to 120A with less than 85% load
Up to 80A with 100% load
Battery Shunt Trip 48 Vdc