Chapter 10

Product Specifications

10.1Model Numbers

The UPS is housed in a free-standing cabinet, divided into two sections with safety shields behind the door and front panels. The UPS is available in 50 or 60 Hz with various output power ratings.

Models

Power Rating

Frequency

 

 

 

Powerware 9395−1100/1000 (four UPM)

1000 kVA

50/60 Hz

 

 

 

Powerware 9395−1100/1100 (four UPM)

1100 kVA

50/60 Hz

 

 

 

Powerware 9395−1100/650 (three UPM)

650 kVA

50/60 Hz

 

 

 

Powerware 9395−1100/750 (three UPM)

750 kVA

50/60 Hz

 

 

 

Powerware 9395−1100/825 (three UPM)

825 kVA

50/60 Hz

 

 

 

The following sections detail the input, output, environmental, and battery specifications for the UPS.

10.2 Specifications

10.2.1 UPS Input

Operating Input Voltage

480 Vac

 

 

Operating Input Frequency Range

50/60 Hz

 

 

Operating Input Current

See Table 3-4on page 3−9 or Table 3-5on page 3−10 for four UPM

 

models.

 

See Table 3-6on page 3−11 or Table 3-7on page 3−12 for three UPM

 

models.

 

Reduced for Generator

 

Adjustable

 

 

Input Current Harmonic Content

5% THD at full load

 

 

Power Factor

Minimum 0.99

 

 

Line Surges

6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4

 

 

Battery Voltage

480 Vdc

 

 

Battery Charging Capacity

Configurable per UPM at nominal line voltage:

 

Up to 120A with less than 85% load

 

Up to 80A with 100% load

 

 

Battery Shunt Trip

48 Vdc

 

 

EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com