UPS OPERATING INSTRUCTIONS
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−17
7.3.10 Using the UPS LOAD OFF Pushbutton or Command
A UPS Load Off is initiated by the LOAD OFF pushbutton from the main menu bar, the
Load Off command on the UPS Control Command screen, or Load Off command on
the Bypass Control Command screen. The UPS LOAD OFF controls the UPS output by
powering down the UPS and de-energizing the critical load.
The UPS (including Bypass) remains off until restarted.
To use the LOAD OFF pushbutton:
1. Press the LOAD OFF pushbutton.
The Load Off screen is displayed, providing a choice to proceed or abort the
shutdown.
C A U T I O N
All power to the critical load is lost when the LOAD OFF is selected in the following step. You should use this
feature only when you want to de-energize the critical load.
2. To shut down the UPS, press LOAD OFF from the Load Off menu bar, and hold for
three seconds. To abort the shutdown, press CANCEL.
When LOAD OFF is selected and held for three seconds, the input, output,
battery, and bypass backfeed contactors open, and the power module is turned
off.
C A U T I O N
Do not attempt to restart the system after Load Off until the cause of the shutdown has been identified and
cleared.
3. To restart the UPS after pressing the LOAD OFF pushbutton, follow the procedure
in paragraph 7.3.1 on page 7−11 or 7.3.2 on page 7−12.
W A R N I N G
Power is present inside the UPS cabinet sections until the upstream input feeder circuit breaker is opened.
To use the LOAD OFF command:
1. Press the CONTROLS pushbutton on the main menu bar. The System Status
screen is displayed.
2. On the System Status screen, select either the UPS or the BYPASS command.
3. Press the CONTROLS pushbutton on the System Status menu bar. The UPS or
Bypass Control Command screen is displayed.
4. On the Control Command screen, select LOAD OFF.
5. Press the SELECT pushbutton on the Command menu bar.
The Load Off screen is displayed, providing a choice to proceed or abort the
shutdown.