UPS INSTALLATION PLAN AND UNPACKING

For four UPM external wiring requirements, including the minimum AWG size of external wiring, see Table 3-4for installations using a common battery system or Table 3-5for installations using a separate battery system. Wire sizes listed are for copper wiring only.

For three UPM external wiring requirements, including the minimum AWG size of external wiring, see Table 3-6for installations using a common battery system or Table 3-7for installations using a separate battery system. Wire sizes listed are for copper wiring only. Because of the future upgradability to a fully rated 1100 kVA UPS with the addition of the FI−UPM, the UPS wiring is specified only for 1100 kVA in Table 3-6and Table 3-7.

Table 3-4. Input/Output Ratings and External Wiring Requirements for the Four UPM Powerware 9395−1100/1000 and 9395−1100/1100

– Common Battery

 

Units

Rating 50/60 Hz

Basic Unit Rating

 

 

 

kVA

1000

1100

 

kW

909

1000

Input and Output Voltage

Volts

480/480

480/480

 

 

 

 

AC Input to UPS Rectifier (0.98 Minimum pF)

Full load current plus battery recharge current

(3) Phases, (1) Ground

Amps

1280

1500

A

Minimum Conductor Size

 

AWG or kcmil

500

500

Number per Phase

 

(each)

(5)

(5)

 

 

 

 

 

AC Input to UPS Bypass (Four Wire)

 

 

 

 

Full Load Current

 

Amps

1203

1323

(3) Phases, (1) Ground

B

 

 

 

 

 

Minimum Conductor Size

 

AWG or kcmil

500

500

Number per Phase

 

(each)

(4)

(5)

 

 

 

 

 

AC Input to UPS Bypass (Five Wire)

Full Load Current

(3) Phases, (1) Neutral, (1) Ground

Amps

1203

1323

B

Minimum Conductor Size

 

AWG or kcmil

500

500

Number per Phase

 

(each)

(5)

(6)

 

 

 

 

 

DC Input from Battery Disconnect to UPS

 

Total Amps

2000

2203

(1) Positive, (1) Negative

 

C

 

 

 

 

 

 

 

Minimum Conductor Size

AWG or kcmil

500

500

 

Number per Pole

 

(each)

(8)

(9)

 

 

 

 

 

AC Output to Critical Load (Four Wire)

 

 

 

 

Full Load Current

 

Amps

1203

1323

(3) Phases, (1) Ground

D

 

 

 

 

 

Minimum Conductor Size

 

AWG or kcmil

500

500

Number per Phase

 

(each)

(4)

(5)

 

 

 

 

 

AC Output to Critical Load (Five Wire)

Full Load Current

(3) Phases, (1) Neutral, (1) Ground

Amps

1203

1323

D

Minimum Conductor Size

 

AWG or kcmil

500

500

Number per Phase

 

(each)

(5)

(6)

 

 

 

 

 

Neutral Bonding Jumper (Four Wire Output Only)

 

 

 

 

Minimum Conductor Size

AWG or kcmil

250

2500

Number

 

(each)

(1)

(1)

NOTE Callout letters A, B, C, and D map to Figure 6-5on page 6−7.

EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com

3−9

Page 29
Image 29
Powerware 10001100 kVA operation manual Common Battery