INSTALLING OPTIONS AND ACCESSORIES

Terminal TB1 Signal Connections from the UPS

Ground

Terminal

Terminal TB3

120 Vac Power

Figure 5-7. Remote Monitor Panel II and Relay Interface Module II Terminal Locations

Ground Terminal

Neutral

120 Vac from

UPS Can Card J3

Line

RMP II, RIM II, or SCM II

Critical Bus

Twisted Pair

Figure 5-8. Remote Monitor Panel II, Relay Interface Module II, or Supervisory Contact Module II Wiring

Table 5-5. RMP II, RIM II, or SCM II Wiring Terminations

From

To

Tightening Torque

Remarks

UPS CAN Card

RMP II, RIM II, or SCM II

Nm (lb in)

 

 

 

 

 

 

 

 

 

 

 

 

 

J3–6 (TX)

TB1–5 (RDX*)

0.9 (8)

 

 

 

 

 

 

Use twisted pair

J3–7 (TX)

TB1–4 (RDX)

0.9 (8)

 

 

 

 

 

N/A

TB3 Line

0.9 (8)

 

 

 

 

 

N/A

TB3 Neutral

0.9 (8)

 

 

 

 

 

N/A

Ground Terminal

2.7 (24) Maximum

 

 

 

 

 

 

 

5−10

EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com

Page 94
Image 94
Powerware 10001100 kVA operation manual Ground Terminal Terminal TB3 Vac Power, From Tightening Torque Remarks