COMMUNICATION

Remote Notification differs from the basic Terminal mode with the addition the following functions:

SCall Answer

The Call Answer function allows the user to call into the UPS from a remote location and enter Terminal mode.

SCall Out

The Call Out function allows the UPS to be configured to call either a remote computer or numeric paging service over the phone line. Call Out allows the UPS to call a remote computer and leave a one-line descriptive message of the alarm or notice condition. Numeric paging support allows the UPS to call a paging service and send numeric messages.

SHousekeeping

The Housekeeping function maintains the link between the UPS and modem.

8.5Terminal Mode

In Terminal mode, the user can request the following functions:

NOTE The brackets ([ ]) in the following bullets indicate standard keyboard characters. To use a key combination, hold down the Escape key and press the indicated letter key.

S[ESC] [A] displays the Active Alarms.

S[ESC] [H] displays the Event History.

S[ESC] [N] displays the Node Bits Setup.

S[ESC] [Q] Quit.

8.5.1Display UPS Control Panel

When this function is invoked, a facsimile of the UPS control panel is displayed on the terminal screen. All controls are functional and can control the UPS remotely. The only exception is the Load Off control which requires the operator to press and hold the local control for two seconds to shut down the UPS.

To remotely control the UPS or view UPS information, use the Escape key legend to control the function normally controlled by the control panel softkeys. See paragraph 7.2 on page 7−2,

the control panel.

8−4

EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com

Page 156
Image 156
Powerware 10001100 kVA operation manual Terminal Mode, Display UPS Control Panel