UPS OPERATING INSTRUCTIONS
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−9
Table 7-4. Typical System Status Messages
Function Message
UPS Shutdown; Bypass; Online
Bypass Off; On; Available
Maintenance Bypass Off; On
Charger Charger Off; Charging
UPM (during startup) DC Starting, Charger Off; DC Starting, Close Battery
Breaker; Inverter Starting; Inverter Syncing; Ready; Online
UPM 1
UPM 2
UPM 3
UPM 4 (not displayed on three UPM model)
Offline; Shutdown, Charger Off; Ready; Ready, Charging;
Online, Charger Off; Online, Charging
Table 7-5. Command Menu Operation
Function Subfunction Operation
UPS Control Commands Use the up or down arrow pushbutton to highlight the command function desired, then press the
SELECT pushbutton to execute the command or proceed to further command screens.
Go to Normal Starts the UPS in Normal mode or transfers the UPS to Normal mode from Bypass mode.
Go to Bypass Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from Normal mode.
Load Off Displays the Load Off screen (see paragraph 7.2.8).
Bypass Commands Use the up or down arrow pushbutton to highlight the command function desired, then press the
SELECT pushbutton to execute the command or proceed to further command screens.
Go to Bypass Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from Normal mode.
Go to Normal Starts the UPS in Normal mode or transfers the UPS to Normal mode from Bypass mode.
Load Off Displays the Load Off screen (see paragraph 7.2.8).
Charger Control
Commands
Use the up or down arrow pushbutton to highlight the command function desired, then press the
SELECT pushbutton to execute the command.
Charger On Turns the battery charger on.
Charger Off Turns the battery charger off
UPM Control
Commands
Use the up or down arrow pushbutton to highlight the command function desired, then press the
CONTROLS pushbutton to execute the command.
UPM On Turns the UPM on without transferring the load to Normal mode. The Load is on bypass.
UPM Off Transfers the load to bypass and turns the UPM off.
UPM Go to Normal Turns the UPM on and transfers the load to Normal mode.
Charger On Turns the battery charger on.
Charger Off Turns the battery charger off