UPS SYSTEM INSTALLATION

4.9.3X−Slot Connections

NOTE LAN and telephone drops for use with X−Slot cards must be provided by the customer.

NOTE When installing external wiring to X−Slot cards, conduit must be installed to the UPS cabinet. When installing internal wiring to X−Slot terminals, route the wiring through the internal opening in the X−Slot communication bay.

For installation and setup of an X−Slot card, contact an Eaton service representative (see page 1−8).

To install wiring to connections:

1.If not already installed, install the LAN and telephone drops.

2.Unfasten the front door latch and swing the door open (see Figure 4-1on page 4−2).

3.Remove the right interface entry conduit landing plate to drill or punch holes (see Figure 4-16on page 4−18).

4.Reinstall the interface entry plate and install the conduit.

5.Route and install the LAN, telephone, and other cables to the appropriate X−Slot cards. See Figure 4-22on page 4−27 and Figure 4-28for X−Slot communication bay locations.

6.Close the door and secure the latch.

7.Refer to the manual supplied with the X−Slot card for operator instructions.

X−Slot Communication Bay 1

X−Slot Communication Bay 2

X−Slot Communication Bay 3

X−Slot Communication Bay 4

 

 

Figure 4-28. X−Slot Communication Bays

EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com

4−33