UPS SYSTEM INSTALLATION

Cable 1G3 Red

UPM 1 (1E4A)

Cable 1G3 Red

 

 

Cable 2G3 Red

+

DC Input to UPMs

UPM 2 (2E4A)

Cable 2G3 Red

 

 

Cable 3G3 Red

UPM 3 (3E4A)

Cable 3G3 Red

+

+

+

Cable 1G3 Black

UPM 1 (1E5A)

Cable 1G3 Black

Cable 2G3 Black

 

UPM 2 (2E5A)

– DC Input to UPMs

Cable 2G3 Black

 

Cable 3G3 Black

UPM 3 (3E5A)

Cable 3G3 Black

Figure 4-10. ISBM Section Battery Input Power Terminal Detail

UPM 1 Cable 1G4 & 1G5 Orange

UPM 2 Cable 2G4 & 2G5 Orange

Phase A (E9A)

UPM 3 Cable 3G4 & 3G5 Orange

UPM 1 Cable 1G4 & 1G5 Brown

UPM 2 Cable 2G4 & 2G5 Brown

Phase B (E10A)

AC Output

from UPMs

 

 

UPM 3 Cable 3G4 & 3G5 Brown

UPM 1 Cable 1G4 & 1G5 Yellow

UPM 2 Cable 2G4 & 2G5 Yellow

Phase C (E11A)

UPM 3 Cable 3G4 & 3G5 Yellow

UPM 1 Cable 1G4 & 1G5 Gray

UPM 2 Cable 2G4 & 2G5 Gray

Neutral from

UPMs (E12A)

 

UPM 3 Cable 3G4 & 3G5 Gray

NOTE Two cable lugs will be connected to each terminal stud. When connecting the cable lugs, install the first lug on the stud with the raised barrel portion facing the back of the cabinet. Install the second lug with the raised barrel portion facing the front of the cabinet.

Figure 4-11. ISBM Section Output Power Terminal Detail

EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com

4−13