UPS INSTALLATION PLAN AND UNPACKING
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−13
Table 3-8. UPS Intercabinet Power Cable Terminations for the Four UPM Powerware 9395−1100/1000 and 9395−1100/1100, and the Three UPMPowerware 9395−1100/650, 9395−1100/750, and 9395−1100/825
Terminal Function Terminal Function Bus Landing Tightening Torque
Nm (lb ft) Stud
AC Input to UPM Section
E1A (UPM 1)
E1A (UPM 2)
E1A (UPM 3)
E1A (UPM 4 – Four UPM Model)
Phase A 3 – stud mounting 12 (8.3) M8
E2A (UPM 1)
E2A (UPM 2)
E2A (UPM 3)
E2A (UPM 4 – Four UPM Model)
Phase B 3 – stud mounting 12 (8.3) M8
E3A (UPM 1)
E3A (UPM 2)
E3A (UPM 3)
E3A (UPM 4 – Four UPM Model)
Phase C 3 – stud mounting 12 (8.3) M8
AC Output from UPM Section
E9A (UPM 1)
E9A (UPM 2)
E9A (UPM 3)
Phase A 3 – stud mounting 12 (8.3) M8
E10A (UPM 1)
E10A (UPM 2)
E10A (UPM 3)
Phase B 3 – stud mounting 12 (8.3) M8
E11A (UPM 1)
E11A (UPM 2)
E11A (UPM 3)
Phase C 3 – stud mounting 12 (8.3) M8
E12A (UPM 1)
E12A (UPM 2)
E12A (UPM 3)
Neutral 3 – stud mounting 12 (8.3) M8
DC Input to UPM Section
1E4A (UPM 1)
2E4A (UPM 2)
3E4A (UPM 3)
Positive 6 – stud mounting
(2 per UPM) 12 (8.3) M8
1E5A (UPM 1)
2E5A (UPM 2)
3E5A (UPM 3)
Negative 6 – stud mounting
(2 per UPM) 12 (8.3) M8
Table 3-9. Supplied Intercabinet Wiring Terminal Hardware Kit
Part Size Quantity Terminals Used On Eaton Part Number
Flat Washer M8 36 UPM AC Input, UPM Battery Input, UPM AC
Output, and Neutral 180500036−080
Conical Washer M8 36 UPM AC Input, UPM Battery Input, UPM AC
Output, and Neutral 180500037−080
Nut M8 36 UPM AC Input, UPM Battery Input, UPM AC
Output, and Neutral 180200001−05