UPS INSTALLATION PLAN AND UNPACKING
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−13
Table 3-8. UPS Intercabinet Power Cable Terminations for the Four UPM Powerware 9395−1100/1000 and 9395−1100/1100, and the Three UPMPowerware 9395−1100/650, 9395−1100/750, and 9395−1100/825Terminal Function Terminal Function Bus Landing Tightening Torque
Nm (lb ft) Stud
AC Input to UPM Section
E1A (UPM 1)
E1A (UPM 2)
E1A (UPM 3)
E1A (UPM 4 – Four UPM Model)
Phase A 3 – stud mounting 12 (8.3) M8
E2A (UPM 1)
E2A (UPM 2)
E2A (UPM 3)
E2A (UPM 4 – Four UPM Model)
Phase B 3 – stud mounting 12 (8.3) M8
E3A (UPM 1)
E3A (UPM 2)
E3A (UPM 3)
E3A (UPM 4 – Four UPM Model)
Phase C 3 – stud mounting 12 (8.3) M8
AC Output from UPM Section
E9A (UPM 1)
E9A (UPM 2)
E9A (UPM 3)
Phase A 3 – stud mounting 12 (8.3) M8
E10A (UPM 1)
E10A (UPM 2)
E10A (UPM 3)
Phase B 3 – stud mounting 12 (8.3) M8
E11A (UPM 1)
E11A (UPM 2)
E11A (UPM 3)
Phase C 3 – stud mounting 12 (8.3) M8
E12A (UPM 1)
E12A (UPM 2)
E12A (UPM 3)
Neutral 3 – stud mounting 12 (8.3) M8
DC Input to UPM Section
1E4A (UPM 1)
2E4A (UPM 2)
3E4A (UPM 3)
Positive 6 – stud mounting
(2 per UPM) 12 (8.3) M8
1E5A (UPM 1)
2E5A (UPM 2)
3E5A (UPM 3)
Negative 6 – stud mounting
(2 per UPM) 12 (8.3) M8
Table 3-9. Supplied Intercabinet Wiring Terminal Hardware KitPart Size Quantity Terminals Used On Eaton Part Number
Flat Washer M8 36 UPM AC Input, UPM Battery Input, UPM AC
Output, and Neutral 180500036−080
Conical Washer M8 36 UPM AC Input, UPM Battery Input, UPM AC
Output, and Neutral 180500037−080
Nut M8 36 UPM AC Input, UPM Battery Input, UPM AC
Output, and Neutral 180200001−05