INSTALLING OPTIONS AND ACCESSORIES
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 5−5
UPS 1 UPS 2 UPS 3 UPS 4
CAN
(If Installed) (If Installed)
Pull Chain
NOTE This drawing is for distributed bypass wiring purposes and is not a floor layout plan. UPSs can be placed in any physical order.
Figure 5-3. Distributed Bypass System Can and Pull−Chain Simplified Interface Wiring
Shielded Twisted Pair
Shielded Twisted Pair Shielded Twisted Pair
UPS 1
CAN Bridge Card J3
UPS 2
CAN Bridge Card J3
UPS 3
CAN Bridge Card J3
(If Installed)
UPS 4
CAN Bridge Card J3
(If Installed)
NOTE External CAN connections between UPSs require shielded twisted pair wire.
Figure 5-4. Distributed Bypass System UPS CAN Wiring without MOBsTable 5-2. CAN Bridge Card Wiring Terminations
From
UPS 1 CAN Bridge Card
To
UPS 2 CAN Bridge Card
To
UPS 3 CAN Bridge Card
(If Installed)
To
UPS 4 CAN Bridge Card
(If Installed)
J3–8 (L) J3–8 (L) J3–8 (L) J3–8 (L)
J3–9 (H) J3–9 (H) J3–9 (H) J3–9 (H)
J3–10 (Shield) J3–10 (Shield) J3–10 (Shield) J3–10 (Shield)