UPS INSTALLATION PLAN AND UNPACKING
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
3−16
Conduit sizes were chosen from NEC Table 4, Electrical Metallic Tubing (EMT). SeeTable 3-13 for conduit requirements.Per NEC article 300, 3(B)(1), all three-phase conductors must be run in the sameconduit. Neutral and ground must be run in the same conduit as the phaseconductors.Conduit is sized to accommodate one neutral conductor the same size as the phaseconductor and one ground conductor sized in accordance with NEC Table 250.122.Conduit sizes listed are for copper wiring only.

Table 3-13. Power Cable Conduit Requirements

UPS Model Voltage Terminal Number of Wires
in Conduit
Minimum Conduit
Trade Size
Number of
Conduits
Powerware 9395−1100/1000
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground) 4 3 5
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground) 4 3 4
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground) 5 3 5
DC Battery
(Positive, Negative, Ground) See Note
Powerware 9395−1100/1100
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground) 4 3 5
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground) 4 3 5
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground) 5 3-1/2 6
DC Battery
(Positive, Negative, Ground) See Note
Powerware 9395−1100/650
Powerware 9395−1100/750
Powerware 9395−1100/825
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground) 4 3 4
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground) 4 3 4
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground) 5 3 5
DC Battery
(Positive, Negative, Ground) See Note
NOTE Select conduit taking into consideration the DC input wire sizes listed in Table 3-4, Table 3-5, Table 3-6, or Table 3-7 starting on page 3−9, the DC
terminations listed in Table 3-10 on page 3−14, type of battery installation, and requirements from NEC Table 4, Electrical Metallic Tubing (EMT).