Initial Configuration

INSTALLATION

Initial Configuration

This section describes how to use the supplied software configuration tool to perform initial configuration and calibration. You can use either the tool or the optional display (if installed) to configure the panels and breakers.

After initial configuration, interface with the EMS−UGK using a Web page interface, the Advanced Metering monitoring system, or (if the optional display is installed) directly through the display.

Installing the Software Configuration Tool

NOTE For best results, install the software configuration tool on a computer running the

Microsoft® Windows® XP or Windows 2000 operating system.

To install the software configuration tool:

1.Connect a computer to the service port on the electronics module using the supplied DB−9 to RS−232 serial cable.

2.Set the computer’s COM port settings to COM1, 19200 baud.

3.Verify that the computer’s settings for the date and time are correct. The configuration tool uses the computer’s settings to automatically set the date and time for the EMS−UGK. You can disable this feature later if needed.

4.Insert the EMS Configuration Tool CD into the computer’s CD drive. The installation program begins automatically within 10 seconds.

If the installation program does not begin automatically, run the CD_Menu.exe program on the CD.

5.Follow the installation program instructions to install the tool.

6.Continue to the following section,

EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com