OPERATION
6.When the individual circuit configuration is complete, select OK to return to the PANEL SCHEDULE screen to configure the next breaker.
7.When all branch circuit configuration is complete, select the
button repeatedly to reach the main menu.
8.If all configuration is complete, save your changes by pressing the Reset button on the Power Xpert Gateway Card in the X−Slot communication bay. (The card automatically resets after five minutes.)
To remove a breaker from the panel:
1.If not already obtained, access the System Setup Level 1 password level. See
2.From the main menu, select METER then PANEL.
3.Highlight the panel number (PNL), and then select SCHEDULE.
4.Highlight the breaker to remove, and then select BREAKER and
DELETE.
5.Select the button repeatedly to reach the main menu.
6.If all configuration is complete, save your changes by pressing the Reset button on the Power Xpert Gateway Card in the X−Slot communication bay. (The card automatically resets after five minutes.)
To change a breaker’s settings:
1.If not already obtained, access the System Setup Level 1 password level. See
2.Follow the steps to remove a breaker from the panel.
3.Follow the steps to configure a breaker.