Powerware 415/240V Harness Connections at the Electronics Module, EMS−UGK Harness Connections

Models: 415/240V 380/220V 208/120V 400/230V

1 72
Download 72 pages 60.53 Kb
Page 22
Image 22
Main Input Harness CTM

INSTALLATION

4.Connect the circular connector of each harness to the electronics module. Verify the harness label matches the connector label on the electronics module. See Figure 6 and Table 5. Figure 7 shows a detailed view of both panels.

NOTE To connect a harness to the electronics module, align the polarizing keys and keyways and insert the plug into the receptacle. Rotate the attached coupling ring clockwise until it snaps into position.

Branch Circuit Harness CT1

CT1

CT1

Branch Circuit Harness CT2

CT2

CT2

Main Input Harness CTM

CTM

CTM

Voltage Harness V1

V1

V2

Figure 6. Harness Connections at the Electronics Module

Table 5. EMS−UGK Harness Connections

Connection

Description

 

 

CT1

Branch circuit harness from Panel 1 / Input 1 to Panel 1 breaker poles 1–21.

 

Dual panel option only. Branch circuit harness from Panel 2 / Input 2 to Panel 2 breaker poles 1–21.

 

 

CT2

Branch circuit harness from Panel 1 / Input 1 to Panel 1 breaker poles 22–42.

 

Dual panel option only. Branch circuit harness from Panel 2 / Input 2 to Panel 2 breaker poles 22–42.

 

 

CTM

Main input monitoring option only. Main input harness from Panel 1 / Input 1 to Panel 1 main

 

connections.

 

Dual panel option only. Main input harness from Panel 2 / Input 2 to Panel 2 main connections.

 

 

V1

Voltage harness from Panel 1 / Input 1 to Panel 1 reference voltage connection.

 

 

V2

Dual panel option only. Voltage harness from Panel 2 / Input 2 to Panel 2 reference voltage

 

connection.

 

 

16 EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com