Installing the Hardware

INSTALLATION

Installing the Hardware

NOTE Review the wiring planning requirements in Step 3 on page 14 as an aid to locating an appropriate site for the EMS−UGK.

To install the EMS−UGK on a wall:

1.Verify that the wall on which the EMS−UGK is to be mounted meets the recommendations listed in Table 1.

Table 1. Wall Specifications (Customer−Supplied Components)

Component

Specification

 

 

Wall surface and

Sufficient to support the weight of the EMS−UGK and installed

wall anchors

cables (see Table 12 on page 57 for weight specifications)

 

 

Clearance around

Above: 102 mm (4") [152 mm (6") recommended]

electronics module

Below: 102 mm (4")

 

Sides: 152 mm (6")

 

 

2.Loosen the four front screws, and remove the four rear screws. Remove the mounting bracket from the electronics module. Retain the bracket and four removed screws. See Figure 2.

M4 10 screws

(8 places)

Figure 2. Mounting Bracket and Electronics Module (with Optional Display)

10 EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com