Powerware 415/240V, 400/230V, 380/220V Configure the following settings for the selected panel

Models: 415/240V 380/220V 208/120V 400/230V

1 72
Download 72 pages 60.53 Kb
Page 38
Image 38
4.Configure the following settings for the selected panel:

INSTALLATION

4.Configure the following settings for the selected panel:

Panel Setting

Description

 

 

Panel Rating

Specify the panel breaker rating (in amps).

 

NOTE Setting the panel breaker rating to 0 silences all

 

main panel breaker alarms and zeroes the panel percent

 

current levels.

 

 

Panel Warn (%)

Specify the warning threshold level (in percent load).

 

 

Panel Alarm (%)

Specify the alarm threshold level (in percent load).

 

 

Num Brkr Positions

Specify the number of breakers in the panel.

 

 

Panel Name

Specify a panel name (up to 19 characters).

 

 

Panel Serial Number

Specify the panel’s serial number (up to 19 characters).

 

 

Panel Layout

Specify the panel numbering style.

 

NOTE Changing panel layout erases all branch circuit

 

breaker configurations.

 

 

NOTE To revert any changes made on the current page back to default settings before saving, click Reload Panel Config.

5.Click Save Panel Config to save the settings to the EMS−UGK. Depending on communication speed, updates take effect within 15–20 seconds.

6.Repeat Steps 3 through 5 to configure the remaining panels.

7.Click the Breaker Config tab to display the Breaker Settings page. The tool automatically updates the default breaker schedule with the latest information from the EMS−UGK. Depending on communication speed, updates take effect within 15–20 seconds.

8.Select the Panel Number of the panel containing the breakers to configure. The tool automatically updates the selected breaker schedule with the latest information from the EMS−UGK.

Depending on communication speed, updates take effect within 15–20 seconds.

32 EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com