Powerware 208/120V, 400/230V, 380/220V Configure the following settings for the selected breaker

Models: 415/240V 380/220V 208/120V 400/230V

1 72
Download 72 pages 60.53 Kb
Page 39
Image 39
10.Configure the following settings for the selected breaker:

INSTALLATION

9.The selected breaker is highlighted in bold in the schedule. The breaker’s configuration details display in the right half of the page.

Click the breaker to configure. The breaker number highlights and its details display at right.

10.Configure the following settings for the selected breaker:

Breaker Setting

Description

 

 

Num Phases

Specify the number of phases (1–3).

 

 

Breaker Rating

Specify the branch breaker rating (in amps).

 

 

Warning Level

Specify the warning threshold level (in percent load).

 

 

Alarm Level

Specify the alarm threshold level (in percent load).

 

 

CT Ratio

Specify the current transformer ratio (75A).

 

NOTE The selected ratio converts to the value 71.9.

 

 

NOTE To revert any changes made on the current page back to default settings before saving, click Reload Breaker Config.

11.Repeat Steps 9 and 10 to configure the remaining breakers in the panel.

12.Click Save Breaker Config to save the settings to the EMS−UGK.

13.Repeat Steps 8 through 12 to configure the breakers in the remaining panels.

14.Click Disconnect to disconnect from the EMS−UGK. Verify that Connected" displays at the bottom of the page.

15.Close the software configuration tool and remove the configuration cable.

16.Activate the reset switch on the bottom of the electronics module: hold the switch for 10 seconds or until the display (if installed) turns off, then release the switch.

17.Continue to

EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com

33

Page 39
Image 39
Powerware 208/120V, 400/230V, 380/220V, 415/240V manual Configure the following settings for the selected breaker