OPERATION
Configuring Branch Circuit Breakers
Follow the appropriate steps to configure, remove, or change the branch circuit breakers.
To configure the branch circuit breakers (up to 42 per panel):
1.If not already obtained, access the System Setup Level 1 password level. See
2.From the main menu, select METER then PANEL.
3.On the PANEL screen, select the panel number (PNL) to configure, and then select SCHEDULE.
4.On the PANEL SCHEDULE screen, highlight the individual breaker to configure and then select BREAKER.
Breakers with blank rating (RTNG) values are not yet configured. See
numbering.
5.On the PANEL X BREAKER METERS screen, select CONFIG and then configure the individual breaker’s meter settings:
NOTE Configure a breaker only if its CT is installed.
Default | Range | Meter Setting | Description |
|
|
|
|
1 | PHASES | Number of phases | |
|
|
|
|
20 | RATING | Branch breaker rating (in amps) | |
|
|
| NOTE Subfeed breaker rating range |
|
|
| is |
|
|
|
|
80 | WARNING | Warning threshold level (in percent | |
|
|
| load)* |
|
|
|
|
90 | OVERLOAD | Alarm threshold level (in percent | |
|
|
| load)* |
|
|
|
|
71.9 | CT | CT ratio | |
|
|
|
|
* Alarm automatically turns off when the load drops below the threshold level.